Machine automation controller cpu unit built-in ethernet/iptm port
Hide thumbs Also See for Sysmac NJ-series:
Table of Contents

Advertisement

3 System-defined Variables Related to the Built-in EtherNet/IP Port
Additional Information
Communications Status with Target Node
The communications status with the target node of an NJ/NX-series Controller is shown by the
combination of the values of four system-defined variables.
• _EIP_RegTargetSta (Registered Target Node Information)
• _EIP_EstbTargetSta (Normal Target Node Information)
• _EIP_TargetPLCErr (Target PLC Error Information)
• _EIP_TargetNodeErr (Target Node Error Information)
Value of
_EIP_RegTarget-
Sta
TRUE
FALSE
For the NX-series Controller, the communications status of CIP communications 1 and CIP com-
munications 2 is shown by the combination of the values of four system-defined variables in the
same way as shown in the above table.
• CIP Communications 1
• _EIP1_RegTargetSta (CIP Communications1 Registered Target Node Information)
• _EIP1_EstbTargetSta (CIP Communications1 Normal Target Node Information)
• _EIP1_TargetPLCErr (CIP Communications1 Target PLC Error Information)
• _EIP_TargetNodeErr (Target Node Error Information)
• CIP Communications 2
• _EIP2_RegTargetSta (CIP Communications2 Registered Target Node Information)
• _EIP2_EstbTargetSta (CIP Communications2 Normal Target Node Information)
• _EIP2_TargetPLCErr (CIP Communications2 Target PLC Error Information)
• _EIP_TargetNodeErr (Target Node Error Information)
3-30
Value of
Value of
_EIP_EstbTar-
_EIP_Target-
getSta
PLCErr
TRUE
FALSE
TRUE
FALSE
Disabled
Disabled
Disabled
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Value of
Communications status with target
_EIP_Target-
NodeErr
FALSE
A connection with the target node was
established normally and there is no error
in the target PLC.
TRUE
A connection with the target node was
established but there is an error in the
target PLC.
TRUE
A connection with the target node was
not established normally.
Disabled
The information is not valid because the
target node is not registered.
node