Troubleshooting
6.1.1 Alarm, Warning and Extended Status Word
Bit
Hex
0
1
1
2
2
4
3
8
4
10
5
20
6
40
7
80
8
100
9
200
10
400
11
800
12
1000
13
2000
14
4000
15
8000
16
10000
17
20000
18
40000
19
80000
20
100000
21
200000
22
400000
23
800000
24
1000000
25
2000000
26
4000000
27
8000000
134217728
28
10000000
268435456
29
20000000
536870912
30
40000000
1073741824
31
80000000
2147483648
Table 6.3
The alarm words, warning words and extended staus
words can be read out via serial bus for diagnose. See also
16-94 Ext. Status Word.
WARNING/ALARM 2, Live zero error
Signal on terminal 53 or 60 is less than 50% of value set in
6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current
and 6-22 Terminal 60 Low Current.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Troubleshooting: Check the supply voltage and supply
currents to the frequency converter. The fault may be
caused by mains distortions. Installing Danfoss Line Filter
may rectify this problem.
®
VLT
Micro Drive FC 51 Programming Guide
Par. 16-90
Dec
AlarmWord
1
Brake check
2
Pwr.card temp
4
Earth Fault
8
16
Ctrl.word TO
32
Over Current
64
128
Motor th over
256
Motor ETR over
512
Inverter overload
1024
DC under volt
2048
DC over volt
4096
Short Circuit
8192
16384
Mains ph. loss
32768
"AMT Not OK"
65536
Live zero error
131072
Internal fault
262144
524288
U phase loss
1048576
V phase loss
2097152
W phase loss
4194304
8388608
Control Voltage Fault
16777216
33554432
67108864
Brake resistor short-circuit
Brake IGBT short-circuit
M4/M5: Earth Fault (Desat)
Drive initialised
Mech. brake low
®
MG02C602 - VLT
is a registered Danfoss trademark
Par. 16-92
WarningWord
Pwr.card temp
Ctrl.word TO
Over Current
Torque limit
Motor th over
Motor ETR over
Inverter overload
DC under volt
DC over volt
Mains ph. loss
Live zero error
Current limit
MotorPhaseMissing
Undefined
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
frequency converter trips after a time.
Troubleshooting
Connect a brake resistor
Extend the ramp time
Change the ramp type
Activate the functions in 2-10 Brake Function
Increase 14-26 Trip Delay at Inverter Fault
The fault may be caused by mains distortions. Installing
Danfoss Line Filter may rectify this problem.
Par. 16-94
ExtendedStatusWord
Ramping
AMT running
Start CW/CCW
Slow down
Catch up
Above Feedback High
Below Feedback Low
Output current high
Output current low
Above Frequency High
6
Below Frequency Low
Braking
OVC active
AC brake
Above Reference High
Below Reference Low
Local Ref./Remote Ref.
DatabaseBusy