Parameter Descriptions
0-10 Active Set-up
Option:
[1 ]
Set-up 1
*
[2]
Set-up 2
[9]
Multi
Set-up
0-11 Edit Set-up
4
4
Option:
[1 ]
Set-up 1
*
[2]
Set-up 2
[9]
Active Set-
up
0-12 Link Set-ups
Option:
[0]
Not
linked
[1 ]
Linked
*
0-31 Custom Readout Min Scale
Range:
0.00
[0.00–
*
9999.00 ]
12
VLT
Function:
Set-up 1 is active.
Set-up 2 is active.
Select the active set-up via digital input and/or
bus, see 5-1* Digital Inputs choice [23].
Function:
The Edit Set-up is for updating parameters in
the frequency converter from either LCP or
bus. It can be identical or different from the
Active Set-up.
All set-ups can be edited during operation,
independently of the active set-up.
Update parameters in Set-up 1.
Update parameters in Set-up 2.
Update parameters in set-up selected as
Active Set-up (see 0-10 Active Set-up).
Function:
The link ensures synchronizing of the "not
changeable during operation" parameter values
enabling shift from one set-up to another
during operation.
If the set-ups are not linked, a change between
them is not possible while the motor is running.
Thus the set-up change does not occur until the
motor is coasted.
Leaves parameters unchanged in both set-ups
and cannot be changed while motor runs.
Copy parameters "not changeable during
operation" parameter values into presently
selected Edit Set-up.
NOTE
This parameter cannot be changed while
motor runs.
Function:
It is possible to create a customized
readout related to the output frequency of
the unit. The value entered in 0-31 Custom
Readout Min Scale will be shown at 0 Hz.
The readout can be shown in the LCP
display when in Status Mode or it can be
read in 16-09 Custom Readout
MG02C602 - VLT
®
Micro Drive FC 51 Programming Guide
0-32 Custom Readout Max Scale
Range:
100.0
[0.00–
*
9999.00]
4.1.2 0-4* LCP
The frequency converter can operate in the following three
modes: Hand, Off and Auto.
Hand: The frequency converter is locally operated and does
not allow any remote control. By activating Hand a start
signal is given.
OFF: The frequency converter stops with a normal stop
ramp. When Off is chosen the frequency converter can
only be started by pressing either Hand or Auto on the
LCP.
Auto: In Auto-mode the frequency converter can be
remote controlled (bus/digital).
0-40 [Hand On] Key on LCP
Option:
[0]
Disabled
[1 ]
Enabled
*
0-41 [Off/Reset] Key on LCP
Option:
[0]
Disable Off/Reset
[1 ]
Enable Off/Reset
*
[2]
Enable Reset Only Reset only. Stop (Off) function is
0-42 [Auto On] Key on LCP
Option:
[0]
Disabled
[1 ]
Enabled
*
®
is a registered Danfoss trademark
Function:
It is possible to create a customized readout
related to the output frequency of the unit.
The value entered in 0-32 Custom Readout
Max Scale will be shown at the frequency
programmed in 4-14 Motor Speed High Limit.
The readout can be shown in the LCP
display when in Status Mode or it can be
read in 16-09 Custom Readout
Function:
[Hand On] key has no function.
[Hand On] key is functional.
Function:
[Off/Reset] key has no function.
Stop signal and reset of any faults.
disabled.
Function:
[Auto On] key has no function.
[Auto On] key is functional.