Parameter Descriptions
13-10 Comparator Operand
Array [4]
Option:
[2]
Feedback
[3]
MotorSpeed
[4]
MotorCurrent
[6]
MotorPower
[7]
MotorVoltage
4
4
[8]
DCLinkVoltage DC-link voltage in [V].
[12] AnalogInput53 Expressed as actual value.
[13] AnalogInput60 Expressed as actual value.
[18] PulseInput33
[20] AlarmNumber
[30] CounterA
[31] CounterB
13-11 Comparator Operator
Array [4]
Option:
[0]
Less Than <
[1]
Approxi-
*
mately equals
[2]
Greater Than
>
13-12 Comparator Value
Array [4]
Range:
0.0
[-9999-9999] Enter "trigger level" for variable monitored
*
4.10.4 13-2* Timers
Use the timer results to define an event (13-51 SL Controller
Action) or as boolean input in a logic rule (13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule
Boolean 3).
When timer value has elapsed timer changes state from
False to True.
42
®
VLT
Function:
Feedback in [Hz].
Motor speed in Hz.
Motor current in [A].
Motor power in either [kW] or [hp].
Motor voltage in [V].
Expressed as actual value.
Shows number of the alarm.
Number of counts.
Number of counts.
Function:
Select operator to be used in comparison.
Result of evaluation is True if variable
selected in 13-10 Comparator Operand is
smaller than fixed value in 13-12
Comparator Value. Result is False if variable
selected in 13-10 Comparator Operand is
greater than fixed value in 13-12
Comparator Value.
Result of evaluation is True if variable
selected in 13-10 Comparator Operand is
approximately equal to fixed value in 13-12
Comparator Value.
Inverse logic of option [0].
Function:
by this comparator.
MG02C602 - VLT
Micro Drive FC 51 Programming Guide
13-20 SLC Controller Timer
Array [3]
Range:
0.0 s
[0.0-3600 s] Enter value to define duration of the False
*
4.10.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE/FALSE inputs)
from timers, comtors, digital inputs, status bits and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in 13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
Boolean 3. Define the operators used to logically combine
the selected inputs in 13-41 Logic Rule Operator 1 and
13-43 Logic Rule Operator 2.
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Illustration 4.12
Priority of calculation
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule
Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE/FALSE) of this calculation is
combined with the settings of 13-43 Logic Rule Operator 2
and 13-44 Logic Rule Boolean 3, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [4]
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
InRange
[4]
OnReference
[7]
Out of Current
Range
[8]
BelowILow
®
is a registered Danfoss trademark
Function:
output from programmed timer. A timer is
only False if it is started by an action and
until the given timer value has elapsed.
Par. 13-41
Par. 13-43
Logic Rule Operator 1
Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-44
Logic Rule Boolean 3
Function:
Select first boolean input for selected
logic rule.
Enters False in logic rule.
Enters True in logic rule.
See parameter group 5-4* Relays [5]
for description.
See parameter group 5-4* Relays [7]
for description.
See parameter group 5-4* Relays [8]
for description.
See parameter group 5-4* Relays [12]
for description.
See parameter group 5-4* Relays [13]
for description.