Parameter Descriptions
Current
(mA)
20
0/4
0%
Analogue
Analogue
output
Output
Min Scale
Max Scale
par. 6-93
par. 6-94
Illustration 4.9
6-94 Terminal 42 Output Max. Scale
Range:
Function:
100.00%
Scale maximum output of selected
*
[0.00-200.00%]
analog signal at terminal 42. Set value
to maximum value of current signal
output. Scale output to give a current
lower than 20 mA at full scale; or 20
mA at an output below 100% of
maximum signal value.
If 20 mA is the desired output current
at a value between 0-100% of the full-
scale output, programme percentage
value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20
mA is desired at maximum output
(100%), calculate percentage value as
follows:
desired maximum current
i.e.
10
mA =
®
VLT
Micro Drive FC 51 Programming Guide
100%
Variable
for
output
example:
Speed
(RPM)
mA
20
× 100 %
20
× 100 = 200 %