Parameter Descriptions
5-55 Terminal 33 Low Frequency
Range:
Function:
20 Hz
[20-4999 Hz] Enter low frequency corresponding to low
*
motor shaft speed (i.e. low reference
value) in 5-57 Terminal 33 Low Ref./Feedb.
Value.
5-56 Terminal 33 High Frequency
Range:
Function:
5000 Hz
[21-5000 Hz] Enter high frequency corresponding to
*
high motor shaft speed (i.e. high
reference value) in 5-58 Terminal 33
High Ref./Feedb. Value.
5-57 Terminal 33 Low Ref./Feedb. Value
Range:
Function:
0.000
[-4999-4999] Set reference/feedback value
*
corresponding to low pulse frequency
value set in 5-55 Terminal 33 Low
Frequency.
5-58 Terminal 33 High Ref./Feedb. Value
Range:
Function:
50.000
[-4999-4999] Set reference/feedback value
*
corresponding to high pulse frequency
value set in 5-56 Terminal 33 High
Frequency.
®