Parameter Descriptions
13-01 Start Event
Option:
Function:
[36]
DigitalInput_29
Use value of DI 29 in logic rule.
[38]
DigitalInput_33
[39]
StartCommand
This event is True, if frequency
*
converter is started by any means
(digital input or other).
[40]
DriveStopped
This event is True, if frequency
converter is stopped or coasted by
any means (digital input or other).
13-02 Stop Event
Option:
Function:
Select input to activate Smart Logic
Control.
[0]
False
Enters False in logic rule.
[1]
True
Enters True in logic rule.
[2]
Running
See parameter group 5-4* Relays [5]
for description.
[3]
InRange
See parameter group 5-4* Relays [7]
for description.
[4]
OnReference
See parameter group 5-4* Relays [8]
for description.
[7]
Out of Current
See parameter group 5-4* Relays [12]
Range
for description.
[8]
BelowILow
See parameter group 5-4* Relays [13]
for description.
[9]
AboveIHigh
See parameter group 5-4* Relays [14]
for description.
[16]
ThermalWarning
See parameter group 5-4* Relays [21]
for description.
[17]
MainsOutOfRange
Mains voltage is outside the
specified voltage range.
[18]
Reversing
See parameter group 5-4* Relays [25]
for description.
[19]
Warning
A warning is active.
[20]
Alarm_Trip
A trip alarm is active.
[21]
Alarm_TripLock
A trip lock alarm is active.
[22]
Comparator 0
Use result of comparator 0 in logic
rule.
[23]
Comparator 1
Use result of comparator 1 in logic
rule.
[24]
Comparator 2
Use result of comparator 2 in logic
rule.
[25]
Comparator 3
Use result of comparator 3 in logic
rule.
[26]
LogicRule 0
Use result of logic rule 0 in logic
rule.
[27]
LogicRule 1
Use result of logic rule 1 in logic
rule.
[28]
LogicRule 2
Use result of logic rule 2 in logic
rule.
[29]
LogicRule 3
Use result of logic rule 3 in logic
rule.
[30]
SL Timeout0
Use result of timer 0 in logic rule.
®
VLT
Micro Drive FC 51 Programming Guide
13-02 Stop Event
Option:
[31]
[32]
[33]
[34]
[35]
[36]
[38]
[39]
[40]
13-03 Reset SLC
Option:
[0]
[1]
4.10.3 13-04 Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
Illustration 4.11
In addition, there are digital values that will be compared
to fixed time values. See explanation in 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 toprogramme Comparator
0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Option:
[0]
[1]
®
MG02C602 - VLT
is a registered Danfoss trademark
Function:
SL Timeout1
Use result of timer 1 in logic rule.
SL Timeout2
Use result of timer 2 in logic rule.
DigitalInput_18
Use value of DI 18 in logic rule.
DigitalInput_19
Use value of DI 19 in logic rule.
DigitalInput_27
Use value of DI 27 in logic rule.
DigitalInput_29
Use value of DI 29 in logic rule.
DigitalInput_33
StartCommand
This event is True, if frequency
converter is started by any means
(digital input or other).
DriveStopped
This event is True, if frequency
*
converter is stopped or coasted by
any means (digital input or other).
Function:
Do Not Reset Retains all settings programmed in
*
parameter group 13.
Reset SLC
Reset all group 13 parameters to default
settings.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Function:
Select variable to be monitored by
comparator.
Disabled
Comparator is disabled.
*
Reference
Resulting remote reference (not local) as a
percentage.
4
4
41