Parameter Descriptions
[28] Catch up
Select Catch up/Slow down to increase or
reduce the resulting reference value by the
percentage set in 3-12 Catch Up/Slow Down
Value
[29] Slow down
Same as Catch up [28]
[32] Pulse input
Select Pulse input when using a pulse
(only terminal
sequence as either reference or feedback.
33)
Scaling is done in parameter group 5-5*
Pulse Input
[34] Ramp bit 0
Logic 0=Ramp1, see parameter group 3-4*
Ramp1
Logic 1=Ramp2, see parameter group 3-5*
Ramp2.
[60] Counter A
Input for counter A.
(up)
[61] Counter A
Input for counter A.
(down)
[62] Reset counter
Input for reset of counter A.
A
[63] Counter B
Input for counter B.
(up)
[64] Counter B
Input for counter B.
(down)
[65] Reset counter
Input for reset of counter B.
B
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
Start Select function from available digital input range.
*
See parameter group 5-1* Digital Inputs for choices.
5-11 Terminal 19 Digital Input
Option:
Function:
[10]
Reversing Select function from available digital input
*
range.
See parameter group 5-1* Digital Inputs for
choices.
5-12 Terminal 27 Digital Input
Option:
Function:
[1]
Reset Select function from available digital input range.
*
See parameter group 5-1* Digital Inputs* for choices.
5-13 Terminal 29 Digital Input
Option:
Function:
[14]
Jog Select function from available digital input range.
*
See parameter group 5-1* Digital Inputs for choices.
5-15 Terminal 33 Digital Input
Option:
Function:
[16]
Preset bit 0 Select function from available digital input
*
range.
See parameter group 5-1* Digital Inputs for
choices.
®
VLT
Micro Drive FC 51 Programming Guide
4.6.3 5-3* Digital Outputs
5-34 On delay, Terminal 42 Digital Output
Range:
0.01 s
5-35 Off delay, Terminal 42 Digital Output
Range:
0.01 s
4.6.4 5-4* Relays
Parameter group for configuring timing and output
functions for relays.
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10] Alarm on Warning An alarm or warning activates output.
[12] Out of Current
[13] Below Current,
[14] Above Current,
[16] Below Frequency,
[17] Above Frequency,
[19] Below Feedback,
[20] Above Feedback,
[21] Thermal Warning
®
MG02C602 - VLT
is a registered Danfoss trademark
[0.00-600.00 s]
*
[0.00-600.00 s]
*
No Operation
Default for all digital and relay outputs.
Control Ready
Control board receives supply voltage.
Drive Ready
Frequency converter is ready for
operation and applies supply signal on
control board.
Drive Ready,
Frequency converter is ready for
Remote
operation in Auto On-mode.
Enable/No
Frequency converter is ready for
Warning
operation. No start or stop command is
given. No warnings are present.
Drive Running
Motor is running.
Running/No
Motor runs, and no warning are
Warning
present.
Run in Range/No
Motor runs within programmed current
Warning
ranges, see 4-50 Warning Current Low
and 4-51 Warning Current High. No
warnings are present.
Run on ref/No
Motor runs at reference speed.
Warning
Alarm
An alarm activates output.
Motor current is outside range set in
Range
4-50 Warning Current Low and 4-51
Warning Current High.
Motor current is lower than set in 4-50
low
Warning Current Low.
Motor current is higher than set in 4-51
high
Warning Current High.
Motor speed is lower than set in 4-40
low
Warning Frequency Low.
Motor speed is higher than set in 4-41
high
Warning Frequency High.
Feedback is lower than set in 4-56
low
Warning Feedback Low.
Feedback is higher than set in 4-57
high
Warning Feedback High.
Thermal warning is present when
temperature exceeds limit in motor,
frequency converter, brake resistor or
thermistor.
Function:
Function:
4
4
29