Advertisement

5 How to operate the adjustable frequency
drive
NOTE!
Stop the motor before performing any of these operations.
Data storage in LCP:
LCP Copy
1.
Go to par. 0-50
2.
Press the [OK] key.
3.
Select "All to LCP"
4.
Press the [OK] key.
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press [OK].
5
The GLCP can now be connected to another adjustable frequency drive and the parameter settings copied to this adjustable frequency drive.
Data transfer from LCP to adjustable frequency drive:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key.
3.
Select "All from LCP"
4.
Press the [OK] key.
The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive, as indicated by the progress bar. When 100% is reached,
press [OK].
5.1.8 Initialization to Default Settings
There are two ways to initialize the adjustable frequency drive to default: Recommended initialization and manual initialization.
Please be aware that they have different impacts according to the below description.
Recommended initialization (via par. 14-22
1.
Select par. 14-22
2.
Press [OK]
3.
Select "Initialization" (for NLCP select "2")
4.
Press [OK]
5.
Disconnect the power from the unit and wait for the display to
turn off.
6.
Reconnecting the power resets the adjustable frequency drive.
Please note that the first start-up takes a few more seconds.
7.
Press [Reset]
NOTE!
Parameters selected in par. 0-25
Manual initialization
5-6
Operation Mode
Operation Mode
My Personal Menu
MG.11.A9.22 - VLT
)
par. 14-22
Operation Mode
RFI 1
par. 14-50
par. 8-30
Protocol
Address
par. 8-31
Baud Rate
par. 8-32
par. 8-35
Minimum Response Delay
Max Response Delay
par. 8-36
Max Inter-Char Delay
par. 8-37
Operating Hours
par. 15-00
Historic Log: Event
par. 15-20
par. 15-30
Alarm Log: Error Code
will remain present with the default factory setting.
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Instruction Manual
initializes all except:
Over Volts
to par. 15-05
Historic Log: Time
to par. 15-22
to par. 15-32
Alarm Log: Time