To meet ISO 11898, a bus cable with a characteristic impedance of 120 W should be
used. The maximum usable cable length for reliable communication decreases with
increasing transmission speed. As a guide, you can use the following values which we
have measured, but they are not to be taken as assured limits.
General characteristic
Bit rates
Distance with larger
bus connections
Number of nodes
Signal environment
Modulation
Coupling medium
Isolation
Typical differential input im-
pedance (recessive state)
Min. differential input impe-
dance (recessive state)
Absolute max.
voltage range
Grounding:
The DeviceNet network must only be grounded at one point, to avoid ground loops. The
circuitry for the physical layer in all devices are referenced to the V-bus signal. The
ground connection is made via the power supply for the bus system. The current flowing
between V- and ground must not flow through any device other than the power supply.
Bus topology:
The DeviceNet medium utilizes a linear bus topology. Termination resistors are required
at each end of the connecting cable. Stub cables are permitted up to a length of 6 meters,
so that at least one node can be connected.
Termination resistors:
DeviceNet requires a termination at each end of the connecting cable.
These resistors must meet the following requirements: 120W, 1% metal-film, ¼ W
132
X15
V-
1
CAN_L
2
Shield
3
CAN_H
4
V+
5
11/2018
Specification
125 kbit, 250 kbit, 500 kbit
500 meters at 125 kBaud
250 meters at 250 kBaud
100 meters at 500 kBaud
64
CAN
Basic bandwidth
DC-coupled differential transmit/receive operation
500 V (option: optocoupler on the transceiver's node side)
Shunt C = 5pF
Shunt R = 25KW (power on)
Shunt C = 24pF + 36 pF/m of the permanently
Shunt R = 20KW
-25 V to +18 V (CAN_H, CAN_L)
The voltages for CAN_H and CAN_L refer to the ground pin
of the transceiver. The voltage is higher than that on the
V-terminal by the amount of the forward voltage drop of the
Schottky diode. This voltage drop must be < 0.6V.
X15
1
2
3
4
5
* according to line impedance about 120 Ù
S748-S772 Instructions Manual
Kollmorgen
attached stub cable
X15
V-
1
CAN_L
2
Shield
3
CAN_H
4
V+
5
X15
1
2
*
3
4
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

S748S700

Table of Contents