Power; Drive Setup For Power And Bus; Operating Voltage; Direct Dc Mains Operation - Kollmorgen AKD PDMM series User Manual

Hide thumbs Also See for AKD PDMM series:
Table of Contents

Advertisement

AKD PDMM User Guide | 6.1   Power

6.1 Power

6.1.1 Drive Setup for Power and Bus

The Power screen allows you to confirm Power Bus settings and accommodates external regeneration
needs if required. Nothing is required for this screen if you have no regeneration requirements. Review the
data on the screen to be certain the bus voltage is at the appropriate levels you expect (approximate input
line AC voltage * 1.4). The other values are the appropriate limits for over voltage and under voltage for the
particular drive. You can select the undervoltage fault mode to trigger either only when the drive is enabled
or always.
From the Power screen, you can view and configure the drive power settings as follows:
Button or Dialog
Box
Measured Bus
Voltage
Over Voltage
Fault Level
Under Voltage
Fault Level
Under Voltage
Fault Mode
Operating Volt-
age
Regen Resistor
Type
Regen Power
External Regen
Resistance
External Regen
Heat Up Time
External Regen
Power
See Regeneration (pg 36) for more information about regen resistors and sizing regen resistors. 

6.1.1.1 Operating Voltage

Operating voltage can be selected by the user to allow AKD PDMM-xxx07 (480Vac) drives to work on
240Vac input supplies.
The VBUS.HALFVOLT parameter has an effect on the following voltage-thresholds:
DC-bus over-voltage threshold (see VBUS.OVFTHRESH (pg 445)).
l
The regen-resistor enable/disable voltage thresholds.
l
The inrush-relay enable/disable voltage thresholds.
l
A power-cycle is needed after changing the value and saving the parameter on the NV memory of the
Drive, since the voltage thresholds mentioned above are read during the boot-sequence of the Drive.

6.1.1.2 Direct DC Mains Operation

Direct DC input is available on all standard AKD PDMM models. The DC input should be run into the AC
input connection. Positive and negative DC lines should use L1 and L2 connections (polarity is not crit-
ical). L1 and L2 connections are found on either the X3 connector or the X4 connector depending on the
model.
34
Kollmorgen™ | December 2012
Description
Reads the current DC bus voltage.
Reads the over voltage fault level.
Reads the under voltage fault level.
Sets under voltage mode.
Sets the operating voltage.
Sets the regen resistor type to either -1-External Regen or 0-
Internal Regen (if available).
Reads the regen power (only visible for external regen).
Sets the external, user-defined regen resistor resistance
(only visible for external regen).
Sets the external regen resistor thermal protection time con-
stant (only visible for external regen).
Sets the regen resistor's power fault level for an external
regen resistor (only visible for external regen).
Parameter
VBUS.VALUE (pg
448)
VBUS.OVFTHRESH
(pg 445)
VBUS.UVFTHRESH
(pg 447)
VBUS.UVMODE (pg
447)
VBUS.HALFVOLT
(pg 445)
REGEN.TYPE (pg
425)
REGEN.POWER (pg
423)
REGEN.REXT (pg
424)
REGEN.TEXT (pg
424)
REGEN.WATTEXT
(pg 426)