Number
Text
2561
Replace the control card.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
3072–5122
Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with the
control board hardware.
5124
Option in slot B: Hardware incompatible with the
control board hardware.
5125
Option in slot C0: Hardware incompatible with the
control board hardware.
5126
Option in slot C1: Hardware incompatible with the
control board hardware.
5376–6231
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
Table 9.4 Internal Fault Codes
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gatedrive card, or the ribbon cable between the
power card and gatedrive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Also check parameter 5-00 Digital
I/O Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For terminal X30/6, check the load connected to terminal
X30/6 or remove the short-circuit connection. Also check
parameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
For terminal X30/7, check the load connected to terminal
X30/7 or remove the short-circuit connection. Check
parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
ALARM 45, Earth fault 2
Ground fault.
Troubleshooting
Check for proper grounding and loose
connections.
Check for proper wire size.
Check the motor cables for short circuits or
leakage currents.
MG06I102
Operating Guide
ALARM 46, Power card supply
The supply for the gate drive on the power card is out of
range.
Troubleshooting
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card.
Troubleshooting
WARNING 48, 1.8 V supply low
The 1.2 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
card.
Troubleshooting
WARNING 49, Speed limit
The warning is shown when the speed is outside of the
specified range in parameter 4-11 Motor Speed Low Limit
[RPM] and parameter 4-13 Motor Speed High Limit [RPM].
When the speed is below the specified limit in
parameter 1-86 Trip Speed Low [RPM] (except when starting
or stopping), the drive trips.
ALARM 50, AMA calibration failed
Contact the Danfoss supplier or Danfoss Service
Department.
ALARM 51, AMA check U
The settings for motor voltage, motor current, and motor
power are wrong.
Troubleshooting
ALARM 52, AMA low I
The motor current is too low.
®
Troubleshooting
ALARM 53, AMA motor too big
®
The motor is too large for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The AMA cannot run because the parameter values of the
motor are outside of the acceptable range.
ALARM 56, AMA interrupted by user
The AMA is manually interrupted.
ALARM 57, AMA internal fault
Try to restart the AMA. Repeated restarts can overheat the
motor.
Danfoss A/S © 06/2018 All rights reserved.
Check for a defective power card.
Contact the Danfoss supplier or Danfoss Service
Department.
Check for a defective control card.
If an option card is present, check for
overvoltage.
and I
nom
nom
Check the settings in parameters 1-20 to 1-25.
nom
Check the settings in parameter 1-24 Motor
Current.
9