8 Wiring Configuration Examples

8.1 Introduction

The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Required switch settings for analog terminals A53
or A54 are also shown.
NOTICE
When not using the optional STO feature, a jumper wire
is required between terminal 12 (or 13) and terminal 37
for the drive to operate with factory default
8
8
programming values.

8.2 Wiring for Open-loop Speed Control

FC
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 8.1 Analog Speed Reference (Voltage)
40
VLT® AutomationDrive FC 361
Parameters
Function
Parameter 6-10 Termi
nal 53 Low Voltage
Parameter 6-11 Termi
nal 53 High Voltage
Parameter 6-14 Termi
+
nal 53 Low Ref./
Feedb. Value
Parameter 6-15 Termi
-
nal 53 High Ref./
0 – 10 V
Feedb. Value
* = Default value
Notes/comments:
Assumptions are 0 V DC input
= 0 Hz speed and 10 V DC
input = 50 Hz speed.
Danfoss A/S © 06/2018 All rights reserved.
FC
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 8.2 Analog Speed Reference (Current)
Setting
FC
0.07 V*
10 V*
+10 V
50
A IN
53
0 Hz
A IN
54
COM
55
A OUT
42
COM
39
50 Hz
U - I
A53
Table 8.3 Speed Reference (Using a Manual Potentiometer)
Parameters
Function
Parameter 6-12 Terminal
53 Low Current
Parameter 6-13 Terminal
53 High Current
Parameter 6-14 Terminal
+
53 Low Ref./Feedb.
Value
Parameter 6-15 Terminal
-
53 High Ref./Feedb.
4 - 20mA
Value
* = Default value
Notes/comments:
Assumptions are 4 mA input =
0 Hz speed and 20 mA input =
50 Hz speed.
Parameters
Function
Parameter 6-12 Terminal
53 Low Current
Parameter 6-13 Terminal
53 High Current
Parameter 6-14 Terminal
≈ 5kΩ
53 Low Ref./Feedb.
Value
Parameter 6-15 Terminal
53 High Ref./Feedb.
Value
* = Default value
Notes/comments:
Assumptions are 0 V DC input
= 0 RPM speed and 10 V DC
input = 1500 RPM speed.
MG06I102
Setting
4 mA*
20 mA*
0 Hz
50 Hz
Setting
4 mA*
20 mA*
0 Hz
50 Hz