Connecting The Ac Mains - Danfoss VLT AutomationDrive FC 361 Operating Manual

90–315 kw, enclosure size j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361:
Table of Contents

Advertisement

Electrical Installation

5.6 Connecting the AC Mains

Size the wiring according to the input current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data,
380-480 V.
Comply with local and national electrical codes for cable sizes.
Procedure
1.
Strip a section of the outer cable insulation.
2.
Position the stripped wire under the cable clamp, establishing mechanical fixation and electrical contact between
the cable shield and ground.
3.
Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions
provided in chapter 5.4 Connecting to Ground.
4.
Connect the 3-phase AC input power wiring to terminals R, S, and T (see Illustration 5.5).
5.
When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg
(grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off to avoid damage to the DC link and to
reduce ground capacity currents.
6.
Tighten the terminals in accordance with the information provided in chapter 10.8 Fastener Tightening Torques.
MG06I102
Operating Guide
Danfoss A/S © 06/2018 All rights reserved.