Electrical Installation

5.9 Control Wiring

All terminals to the control cables are inside the drive
below the LCP. To access the control terminals, either open
the door (D1h/D2h/D5h/D6h/D7h/D8h) or remove the front
panel (D3h/D4h).
5.9.1 Control Cable Routing
Isolate control wiring from high-power
components in the drive.
Tie down all control wires after routing them.
Connect shields to ensure optimum electrical
immunity.
When the drive is connected to a thermistor,
ensure that the thermistor control wiring is
shielded and reinforced/double insulated. A 24 V
DC supply voltage is recommended.
Fieldbus connection
Connections are made to the relevant options on the
control card. For more detail, see the relevant fieldbus
instruction. The cable must be tied down and routed along
with other control wires inside the unit.
5.9.2 Control Terminal Types
Illustration 5.35 shows the removable drive connectors.
Terminal functions and default settings are summarized in
Table 5.1 – Table 5.3.
Illustration 5.35 Control Terminal Locations
MG21A502
Operating Guide
1
2
1
Serial communication terminals
2
Digital input/output terminals
3
Analog input/output terminals
Illustration 5.36 Terminal Numbers Located on the Connectors
Terminal
61
68 (+)
69 (-)
Table 5.1 Serial Communication Terminal Descriptions
Terminal
12, 13
18
19
32
33
Danfoss A/S © 09/2018 All rights reserved.
61
68
69
39
42 50 53 54 55
12 13 18 19 27 29 32 33 20 37
Parameter
Default
setting
Integrated RC-filter for
cable shield. ONLY for
connecting the shield
to correct EMC
problems.
Parameter
RS485 interface. A
group 8-3* FC
switch (BUS TER.) is
Port Settings
provided on the
control card for bus
Parameter
termination
group 8-3* FC
resistance. See
Port Settings
Illustration 5.40.
Digital input/output terminals
Parameter
Default
setting
+24 V DC
24 V DC supply
voltage for digital
inputs and external
transducers.
Maximum output
current 200 mA for all
24 V loads.
Parameter 5-10
[8] Start
Digital inputs.
Terminal 18
Digital Input
Parameter 5-11
[10]
Terminal 19
Reversing
Digital Input
Parameter 5-14
[0] No
Terminal 32
operation
Digital Input
Parameter 5-15
[0] No
Terminal 33
operation
Digital Input
3
5
5
Description
Description
63