Danfoss VLT AQUA Drive FC 202 Operating Manual page 105

Vlt series 110–400 kw, enclosure sizes d1h–d8h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
®
VLT
AQUA Drive FC 202
High/normal load
(High overload=150% current during 60 s.
Normal overload=110% current during 60 s)
Typical shaft output at 525 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload)(at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 525 V) [A]
Continuous (at 575/690 V)
Maximum number and size of cables per phase
- Mains, motor, brake, and load share [mm
Maximum external mains fuses [A]
Estimated power loss at 575 V [W]
Estimated power loss at 690 V [W]
3)
Efficiency
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Table 10.6 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
MG21A502
Operating Guide
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 09/2018 All rights reserved.
N132
HO
NO
90
110
125
150
110
132
D1h/D3h/D5h/D6h
137
162
206
178
131
155
197
171
125
147
131
154
157
185
132
156
126
149
2x95 (2x3/0)
160
1742
2101
1800
2167
0.98
0–590
110 (230)
75 (167)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N160
HO
NO
110
132
150
200
132
160
162
201
243
221
155
192
233
211
147
183
154
191
185
230
156
193
149
185
2x95 (2x3/0)
315
2080
2649
2159
2740
0.98
0–590
110 (230)
75 (167)
103
10
10