7 Installation planning
Clearances needed to allow proper airflow on the UPS system and to allow door opening.
Figure 2: Top view and indication of the minimum clearances for UPS + other cabinets in row.
Table 3: minimum clearances for UPS + other cabinets in row.
PowerWave 33 Series 3 Cabinets
Back clearance for ventilation
A
(forced air outlet)
Front clearance needed to allow a
B
correct door opening
C
Maximum door opening angle
Top Clearance
D
(Top clearance is only needed if
there is no side clearance)
Battery cabinet requires 100mm clearance for natural ventilation. The UPS does not require any back clearance.
4)
Accessibility
Positioning
Power and signals wiring
Modifications reserved
Page 12/15
60 / 80 / 100 / 120
0 mm
Totally front accessible for start-up and maintenance
Strictly indoor in a temperature and humidity controlled environment. The
UPS can be placed against the wall (back side)
Front bottom
UPS + battery cabinets in
row.
100mm
4)
1000 mm
115°
400 mm