ABB PowerWave 33 Series 3 User Manual page 56

60 – 120 kw
Table of Contents

Advertisement

Max slew-rate
Nominal current (In), r.m.s.
rated:
Overload on inverter
Fault clearing capability
normal mode and battery
mode (100ms)
Crest factor (Load supported)
Load power factor, rated
Displacement
(permissible lead-lag range)
AC / AC efficiency in normal mode, linear load:
100% load
75% load
50% load
25% load
Eco-mode efficiency, linear
load
Bypass - automatic: static switch
Transfer time: inverter 
bypass / bypass  inverter / in
eco-mode
Rated current
Fault clearing capability
(bypass mode) for 20 ms
Overload on bypass mode
Bypass - maintenance
Bypass protection fuse or
circuit breaker rating
Modifications reserved
Page 8/15
1
87
116
0.5 @ 150% load; 5 @ 125% load; 20 @ 110% load
2.0 x In
2.0 x In
3: 1
1
(all range) 0
95.5
1)
95.5
1)
95.8
95.8
1)
1)
96.0
1)
96.0
1)
95.0
95.0
1)
1)
≥ 99.0
<1 / <5 / <6
87
116
10 x In
2)
continuously @ 110% load
0.5 @ 150% load
5 @ 125% load
yes, standard
Not included
145
174
2.0 x In
2.0 x In
95.7
1)
95.7
1)
96.0
96.0
1)
1)
96.0
1)
96.0
1)
95.0
95.0
1)
1)
145
174
Hz/s
A
min
A
-
-
%, s
%
%
ms
A
A
min