Output Characteristics - ABB PowerWave 33 Series 3 User Manual

60 – 120 kw
Table of Contents

Advertisement

ADDITIONAL AND USUAL INFORMATION
Connection:
Cable entry:
Accessibility:
Walk In/Soft Start:

4 Output characteristics

PowerWave 33 Series 3
Power, rated:
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
neutral available
Rated voltage
(steady state, r.m.s.)
Variation in
normal mode / battery mode
Total harmonic distortion (THDu), 100% load, normal mode:
Linear
Non-linear
(acc. to IEC 62040-3)
Total harmonic distortion (THDu), 100% load, battery mode:
Linear
Non-linear
(acc. to IEC 62040-3)
Voltage unbalance and phase
displacement,
100% load
unbalance
Voltage transient and recovery time, 100% step load:
Linear
Non-linear
(acc. to IEC 62040-3)
Transfer normal mode -->
battery mode
Frequency (steady-state),
rated:
Variation in normal mode
(frq. Synchronized with mains)
Variation in battery mode
(free-running)
Max synch phase error
(referred to a 360° cycle)
Modifications reserved
Page 7/15
5 wires, 3 phase + N + PE
Bottom
Frontal
Yes
60
80
60
80
3
yes
380 / 220
400 / 230
415 / 240
± 1.5 / ± 1.5
< 2.0
< 4.0 %
< 2.0
< 4.0 %
0
± 4
± 4
0
50 / 60 (selectable)
± 2 / ± 4
± 0.1
<2
100
120
100
120
KW
kW
-
-
VAC
%
%
%
°
%
%
%
Hz
%
°