Input Characteristics - ABB PowerWave 33 Series 3 User Manual

60 – 120 kw
Table of Contents

Advertisement

ADDITIONAL AND USUAL INFORMATION
Connection
Cable entry
Accessibility
Air outlet
Color
Color code
OPTIONS
Battery cabinets
Parallel Kit
SNMP Cards
USB port & Relay card with potential-free contacts (Customer outputs)
Back-feed protection
Single input feed KIT
Sea freight packaging (wooden box)

3 Input characteristics

PowerWave 33 Series 3
Rated voltage
(steady-state, r.m.s)
Tolerance, referred to
400/230V
Frequency, rated
Tolerance, referred to 50Hz
Current (r.m.s), rated
(with battery charged and input
400/230V)
Current (r.m.s), maximum
(with charging batt. and input
400/230V)
Total harmonic distortion
(THDi)
In-rush current
(A or % of nominal)
Power factor
Rated short-time withstand
current (I
)
CW
AC power distribution system: TN-S, TN-C, TN-C-S, TT
note: in static bypass mode or eco-mode TN-C and TN-C-S can cause PE current to rise above 5% of phase currents.
Phases required
Neutral required
Modifications reserved
Page 6/15
5 wires, 3 phase + N + PE
Bottom
Frontal only
Top
Graphite Grey (RAL 7024)
PULVERLACKE NR.4222903402 Ver. 09RCCAT1 ORANGE PEEL
60
80
380 / 220
400 / 230
415 / 240
-10 / +15 at <100% load
-20 / +15 at <80% load,
-30 / +15 at <60% load
50
-30 / +40
92
122
101
134
≤ 4% at 100% load
< 100% of the rated current
0.99 @ 100% load
10 for 1.5 seconds
3
yes
100
120
152
183
167
201
KW
VAC
%
Hz
%
A
A
%
A or %
kA, s

Hide quick links:

Advertisement

Table of Contents
loading