5.1.1 Customer inputs

The customer input interfaces are standard for each model and are located in the front bottom part of
the unit.
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm
Table 8: details of the customer inputs.
Block
Terminal
Contact
GND
X1 / 10
X1 / 9
IN
X1 / 8
GND
X1 / 7
IN
X1 / 6
GND
X1 / 5
IN
X1 / 4
GND
X1 / 3
IN
X1
X1 / 2
GND
X1 / 1
IN
5.1.2 Customer outputs (OPTIONAL USB port & Relay card)
The customer output interfaces are on an optional relay card which goes into slot 2 of the UPS.
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires: 0.5 mm
Table 9: details of the customer outputs + USB on the relay card.
Block
15
1
X2
Modifications reserved
Page 22/50
Signal
Function
GND
12 Vdc source
+12Vdc
(Max 200mA load)
GND
Remote Shut down
+12Vdc
(Do not remove the factory mounted bridge until an external remote shut down is connected)
GND
Temperature Battery
+3.3Vdc
(If connected, the battery charger current is batt. temperature dependent)
GND
Customer IN 1
+12Vdc
(Function on request, to be defined)
GND
GEN_OPERATION
+12Vdc
(NC = Generator ON)
Terminal
Contact
C
X2 / 15
X2 / 14
NC
X2 / 13
NO
C
X2 / 12
X2 / 11
NC
X2 / 10
NO
X2 / 9
C
NC
X2 / 8
X2 / 7
NO
X2 / 6
C
X2 / 5
NC
NO
X2 / 4
X2 / 3
C
X2 / 2
NC
X2 /1
NO
+ USB
Signal
On Display
ALARM
COMMON_ALARM
Message
LOAD_ON_MAINS
ALARM
BATT_LOW
Message
LOAD_ON_INV
ALARM
MAINS_OK
2
2
Function
Common
NO Alarm Condition
Common Alarm
(System)
Common
(Load on Inverter)
Load on bypass (Mains)
Common
Battery OK
Battery Low
Common
(Load on Mains bypass)
Load on Inverter
Common
Mains Failure
Mains Present