4.3 Block diagram

Figure 12: Block diagram of PowerWave 33 S3. On the left with single input feed configuration and on the right with dual

4.4 Wiring

Before proceeding to wire the UPS, make sure that you have read and understood the chapter above
4.2 Electrical installation and make sure that the following is respected:
The cable sections and fuse ratings are respecting the local standards. Alternatively, you can
use the recommended cable sections and fuse rating in the tables 6 and 7, which are according
to (IEC 60950-1).
Table 5: SINGLE INPUT FEED (CABLE LINKS TO ACHIEVE SINGLE INPUT ARE OPTIONAL)
Fuse A
Rated
Type:gL or
output
CB
power
(quantity x A)
60 kW
3x100
80 kW
3x125
100
3x160
kW
120
3x200
kW
Modifications reserved
Page 17/50
input feed configuration.
Cable A
Cable D
(quantity x
(quantity x
mm
2
)
mm
2
)
5x(1x35)
5x(1x35)
5x(1x50)
5x(1x50)
5x(1x70)
5x(1x70)
5x(1x95)
5x(1x95)
Fuse E
Type:gR or
CB
(quantity x mm
(quantity x A)
2x160
2x(1x95) @ 42-45 batt. blocks
2x200
2x(1x70) @ 46-50 batt. blocks
2x(1x120) or 2x(2x50) @ 42-45 batt.
2x250
2x(1x95) @ 46-50 batt. blocks
2x(1x150) or 2x(2x50) @ 42-45 batt.
2x300
2x(1x120) or 2x(2x50) @ 46-50 batt.
Cable E
)
2
2x(1x50)
blocks
blocks
blocks