Page 1
ENGINEERING TOMORROW PVED-CLS Controller For Electrohydraulic Steering User Manual Software version 2.01...
Page 2
ENGINEERING TOMORROW Important User Information Danfoss is not responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included for illustration purposes. Due to the many variables and requirements associated with any particular installation, Danfoss cannot assume responsibility or liability for the actual used bases on the examples and diagrams.
Increasing demand shows a trend for a higher safety-level up to AgPl “d” for off-road driving. In order to give this functionality Danfoss has developed the PVED-CLS. The PVED-CLS is based on Danfoss PVE technology, as used in electro hydraulic proportional valves for decades. PVE modules are used with PVG spool valves and dedicated spool valves for steering applications, OSPE and EHPS as well as the EHi-E and EHi-H systems.
Missing curvature commands are exceptions and does not put PVED-CLS to safe state. A reset may be either a power cycle sequence or a soft reset CAN message. For more details, please see the Danfoss document- PVED-CLS communication Protocol.
Page 14
Figure 3 EHi-H System In a OSPE (Figure 1) and EHi-E (Figure 2) with PVED-CLS, a Danfoss SASA-sensor and a two channel vehicle speed sensor, a MMI interface (for changing programs, steering devices, steering modes etc.) on the CAN bus are prerequisite in order to complete the OSPE and EHi-E systems.
Page 15
Valid Values: 0 (OSPE, EHi-E); 1 (EHPS); 2 (EHi-H) OSP displacement, number of cubic centimeters per revolution OSP displacement P3084 Note: When the PVED-CLS is mounted on an EHPS this parameter must be set equal to 0! Cylinder stroke volume. Acceptable values: 100-10000.
When the PVED-CLS is mounted on an EHPS the cut-off valve is not present, therefore P3072 needs to be 0 and the valve type needs to be set to EHPS by setting P3081 to 1. Furthermore, as the flow direction in an EHPS compared to OSPE/EHi- E and EHi-H is inverted, the PVED-CLS need to be provided with this information, which can be done by setting P3080 to 255.
Page 17
(hence pure hydraulic Resolution: 0.01 turns) OSP displacement, number of cubic centimeters per revolution OSP displacement P3084 Note: When the PVED-CLS is mounted on an EHPS this parameter 1200 must be set equal to 0! Cylinder stroke volume. Acceptable values: 100-10000.
Figure 5 shows the high level steering mode selection state machine. The state transition requirements are described in detail in chapter 3.6. The operational states of PVED-CLS can be observed in ‘Operation status message’, (refer PVED-CLS Communication Protocol document for more details).
P3254 (SASA or IMD), the further transition of states is determined for steering with SASA or steering with IMD. In Steering wheel program 1 – 5, the EH-Valve is active and the PVED-CLS behavior can be configured individually. Find additional information on how to setup the programs in chapter 10.
Figure shows the AUX steering device state machine. When the AUX device is configured to be a steering wheel, PVED-CLS offers 5 individually configurable steering programs. If the AUX device is configured to be a joystick, only 1 program is available. Find more information regarding AUX devices and the configuration in chapter 11.
The PVED-CLS detects the AUX open loop device to be in use when, The AUX steering device is present in the system – P3239 set to 255 The AUX steering device is enabled – see flags in the MMI messages in PVED-CLS communication protocol, 1.
Page 25
The PVED-CLS detects the AUX closed loop joystick to be enabled when, The AUX steering device is present in the system – P3239 set to 255 The AUX steering device is enabled – see flags in the MMI messages in PVED-CLS communication protocol, The AUX steering device is a closed loop joystick –...
- Max. CL steady state error threshold) for at least the time specified threshold value for P3731 (AUX joystick - Min time for CL steady state error threshold) The closed loop joystick is inactive – see flags in the AUX messages in PVED-CLS communication protocol 3.6.3...
Table 3 Attention Unlock codes, for the different user levels, are managed by Danfoss technical support team and can only be aquired by directly contacting the Danfoss technical support team! Danfoss has developed a service tool (PLUS+1 SERVICE TOOL), and recommend the tool for: •...
Page 29
Test Automatic spool calibration and verify safety setup of vehicle For learning more of how the PLUS+1 SERVICE TOOL works, please go to the Danfoss Power Solution home page. For using other tools than PLUS+1 SERVICE TOOL to manually changing parameters and updating sector- and signature CRC’s in the EEPROM, please refer to the Danfoss document: PVED-CLS KWP2000 Protocol.
ENGINEERING TOMORROW Installation CONNECTOR INTERFACE The PVED-CLS is only available with one connector variant: 12 pin Deutsch DT04-12PA-B016 connector Figure 11 Important Deutsch assembly and installation guidelines must be followed for connector and harness. Accordingly, Danfoss recommends the use of lubricant (e.g. Nyogel 760G) on low-voltage electrical Connector contacts to further enhance the robustness against wear (e.g.
ENGINEERING TOMORROW PVED-CLS LED DIAGNOSTIC The PVED-CLS is equipped with a LED (see Figure 12). The LED behavior will inform about the state of the PVED- CLS: State LED behavior Main µC in the bootloader mode Blinking between or Main µC detects the Safety µC in the bootloader mode...
Section 8.1 and section 8.1.1. The wheel angle sensor sub-system can be CAN based or Analogue based. If it is analogue based, WAS may be connected to the analogue input pins of the PVED-CLS; AD1 and AD2 for analogue dual channel sensor sub-system and AD1 for single channel sensor sub-system.
Page 33
Table 5 When mapping a steering device or sensor, the CAN source addresses (Table 6) and PGN’s (Table 7) needs to be set up and checked for correctness. Find additional information about setting up the CAN communication in PVED-CLS communication protocol.
• For more details and wiring schematics, please referrer to the PVED-CLS Safety Manual. • If the PVED-CLS is mounted on a EHPS valve, P3072: Cut-off valve present must be set to 0 (Not present), as the EHPS valve does not have a cut-off valve. If P3072: Cut-off valve present is set to any other value than 0 (Not present), the PVED-CLS enter safe state.
Page 36
ON-OFF control mode, i.e. P3073: Cut-off valve control mode is set to 0 This control algorithm will set the duty cycle of the PWM signal to 100%, when the PVED-CLS is activating the cut-off solenoid valve, this means that the power supply of the cut-off solenoid valve will be equal to the PVED-CLS power supply.
ENGINEERING TOMORROW Important There is no validation in the PVED-CLS that P3074: Cut-off valve CL pull current > P3076: Cut-off valve CL hold current. Important Danfoss recommends not to change the default values for P3074, P3076 and P3097. Contact your local technical support at Danfoss Power Solutions if there is a need to change these parameters.
PVED-CLS does not goes into fail safe mode in cold conditions. • If PVED-CLS is commanded to go to off-road mode before pump pressure is available, PVED-CLS will not be able to perform this self-test and hence fail after the specified timeout set by P3078.
If the fall time is observed longer than specified by P3101: Safety-checks IMD – Maximum fall time, the COV solenoid will be concluded as stuck open and the PVED-CLS will enter safe state. There is no limit on how long the rise time can This check ensures that the cut-off valve can achieve the blocked state, when the cut-off solenoid valve is de-energized.
Page 41
Important Not all combinations of these 3 parameters are valid. If an invalid condition is detected by PVED-CLS, it will enter safe state and notify about an invalid EEPROM configuration of the Peripherals sector. See truth table in Table 11.
When PVED-CLS is in Safe on-road state, this function slowly increases the duty-cycle on the cut-off output. If the current raises above the parameter threshold, specified by P3243, the PVED-CLS goes to safe, because it has detected that the Cut-off coil was not disconnected on the transition to Safe on-road thus reports a relay switch failure.
Important The PVED-CLS is dedicated for IMD: It has built in check valves between pilot ends of the EH spool to the PE pilot supply. In this way, its ensured there will be no hydraulic pressure on either end of the spool when the cut off spool is in safe state, because the pilot supply is connected to tank.
P3090. If the spool is outside this threshold during boot-up and the PVED-CLS is mounted on an OSPE/EHi, the PVED-CLS will go into safe state. If the PVED-CLS is mounted on an EHPS, further checks are done to see if the spool has moved outside the dead-band, a confidence counter level has to be reached before PVED-CLS will go into safe state.
P3248 set to 1 will shut down the sensor supply but not the monitoring of it. So if it is disabled (i.e. P3248 set to 1), an external 5V supply has to be connected to PVED-CLS sensor supply pin (pin 11) else PVED-CLS will go to safe state.
The complete PVED-CLS Steering mode selection state machine is shown in chapter 3.2. Similar to the steering device lock, the PVED-CLS will lock a steering program (AUX or STW), when a vehicle speed threshold of P3251 is exceeded (i.e. the PVED-CLS will ignore any steering program change messages, if the vehicle is traveling faster than the value in P3251).
P3253 indicates at which vehicle speed, the PVED-CLS should go into safe state, if this vehicle speed is exceeded during EH-steering. Important If the PVED-CLS is in Safe ON-Road mode, the PVED-CLS will not go into safe state (SVB and cut-off valve are already de-energized)! Range...
ENGINEERING TOMORROW sensors are absent, then the FDA can be disabled, to avoid PVED-CLS from going into safe state (refer chapter 14, for details on FDA). Furthermore, if the system is an OSPE/EHi-E or EHi-H system, the Cut-off valve must also be connected as a boot-up check is done on the Cut-off Valve presence.
ENGINEERING TOMORROW SASAIID SENSOR Similar to the speed sensor, the PVED-CLS’s relies on a safe steering wheel feedback from the SASAIID sensor (not used in EHi-H system, refer section 7.1.4). The SASAIID sensor is designed to send a redundant CAN-message containing both steering wheel position and steering wheel velocity.
ENGINEERING TOMORROW Calibration A PVED-CLS shall always be calibrated to the valve it is controlling (OSPE, EHPS, EHi-E or EHi-H). This allows cancellation of mechanical, electrical and environmental dependent tolerances. Spool calibration also compensates for the mechanical dead-bands designed into the EH spool. Spool calibration is only required at first installation or after PVED- CLS replacement.
WHEEL ANGLE SENSOR CALIBRATION As per default, a PVED-CLS will boot-up in WAS calibration service mode if P3244 i.e. WAS interface is set to either analogue or CAN. From here either WAS auto-calibration routine from the Danfoss PLUS+1 SERVICE TOOL can be used or a manual WAS calibration can be performed (see 17.6).
• If P3426 is set to a value > 89 and if P3428 is set to a value > 89, that forces the PVED-CLS to calculate and use automatic adjusted values for Maximum steer angle, Left (i.e. P3193 or P3223 will be updated after WAS calibration, depending on WAS-type, by lookup in Table 26), and forces the PVED-CLS to calculate and use automatic adjusted values for Maximum steer angle, Right (i.e.
1.00 Figure 22 ANALOGUE JOYSTICK CALIBRATION As per default, PVED-CLS will boot-up in Analogue joystick calibration service mode after one of the below conditions is reached • If WAS interface i.e.P3244 is set to CAN AND AUX Present i.e. P3239 is set to TRUE and AUX Type i.e. P3240 is set to analogue joystick, and a successful WAS calibration has been completed.
SPOOL CALIBRATION As per default, a PVED-CLS will boot-up in spool calibration service mode after a successful WAS calibration, if WAS interface (i.e. P3244) is set to either analogue or CAN, has been completed. From here either the spool auto-calibration routine from the Danfoss PLUS+1 SERVICE TOOL can be used or a manual spool calibration can be performed, using the direct output control function.
Page 64
Important If WAS is not configured, i.e. parameter P3244, is set to NONE, the calibration cannot be performed and PVED-CLS will signal this in the operation status message. For more details on operational status message, please see the Danfoss document- PVED-CLS communication Protocol.
B. If P3244 is set to 2, P3777 is set to 0 and P3778 set to 255. PVED-CLS will go into Spool calibration service mode if P3244 (WAS interface) is set to 1 or 0, the conditions 1A, 1B and 2A are not fulfilled, P3771 is set to 0 and P3772 is set to 255.
Page 68
P3801: Before automatic spool calibration can be started, the steering wheel has to be armed first. This is to tell the PVED-CLS, that grabbing the steering wheel can be detected, and thus can be used to disengage ongoing spool calibration.
(Capture L, Capture N and Capture R) respectively. It doesn’t matter in which sequence this is done. Danfoss recommends to capture straight position while driving the vehicle slowly, aiming at a spot far away.
Joystick fully left, fully right and back to neutral and press the capture buttons (Capture L, Capture N and Capture R) respectively. It does not matter in which sequence this is done. Danfoss recommends to capture neutral position while driving the vehicle slowly, aiming at a spot far away.
Page 80
ENGINEERING TOMORROW Figure 38 When a successful spool calibration has been achieved, press “Accept and Save” button. PVED-CLS will now store the values in the EEPROM for the following addresses: Range Name Description of parameter Max spool position, left P3162...
Page 81
To use this method the desired parameter changes to P3162, P3164 and P3170 in the valve calibration sector is configured in the hydraulic configuration sector. The PVED-CLS spool auto-calibration routine will copy P3091, P3093 and P3095 to P3162, P3164 and P3170, respectively and calculate the Valve Calibration Data sector CRC.
Steering wheel programs When the PVED-CLS is in Off-road steering mode, one of the 5 different programs can be chosen which can be set with some individual parameters for the steering ratio, and some parameters which are common for all 5 programs such as soft- stop, anti-jerk etc.
10.3 STW IN USE AND ACTIVATION THRESHOLD A steering wheel signal filter has been applied to the PVED-CLS’s steering wheel control algorithm, as a part of risk mitigation, to avoid unintended spool actuation, etc. when driving on bumpy-ground. Practically, any steering wheel signals, i.e. steering wheel signal where the steering angle velocity is below the value in P3521, will be disregarded.
The anti-drift correction volume is calculated by looking at the difference, in degrees, measured at the steering wheel and the actual position of the wheels. How large a percentage of the full flow, the PVED-CLS’s anti-drift algorithm will add, is defined by the following four points, Point A to Point D, where Point B and Point C are configurable.
Page 88
The range is from 1° to 160° for P3568, in steps of 1°. For P3569 the range goes from 0% to 100% in steps of 1%. The values recommended by Danfoss are P3568 set to 20 and P3569 set to 15 i.e. anti-drift will be enabled all the time and 15% of the full flow will be added or deducted, depending on direction, to the calculated ideal ccm per revolution- output, when the difference between the measured steering wheel position and the actual position of the wheels is 20°...
Jerk is a common unpleasant feeling/phenomenon, which can be experienced on large, articulated vehicles. To minimize these jerks, the PVED-CLS has a built-in anti-jerk algorithm which can be enabled and parameterized. Briefly, the Anti-jerk algorithm has two sets of parameters to choose from, one set for when moving away from neutral position and one set for moving towards neutral position.
The range is from 0 to 1000 [IR] for P3562, P3564 and P3566 (i.e. relative wheel angle and soft-stop flow limit, respectively). The values recommended by Danfoss are P3562 set to 400, and P3564 and P3566 set to 0. Important For absolute wheel angles lower than the one specified at Point A maximum flow is available.
ENGINEERING TOMORROW AUX steering When the PVED-CLS is in off-road steering mode (see Figure ) the following steering devices can be chosen: open loop mini wheel steering, open loop joystick steering or closed loop joystick steering. Important Only one type of AUX steering device can be present in the steering system at the same time. AUX steering device is selected by the parameter AUX type (P3240).
If the parameter P3240 is set to Analogue Joystick or open loop joystick or Elobau Joystick i.e. to function in open loop fashion. Then the PVED-CLS will perform a transition to AUX-program if the conditions specified in section 3.6.2 for ‘AUX open loop device’ are met and parameters for selected joystick type are configured correctly (Please see sections 11.8 and 11.9 for parameter configuration of analogue and open loop joystick and...
P3583 and P3584. The PVED-CLS detects that the steering wheel is in use when both the threshold P3583 and P3584 are being exceeded. In order to allow the steering device change to AUX mini wheel, the steering wheel shall not be in use i.e.
OPEN LOOP FILTER As a risk mitigation method, Danfoss wants to avoid unintended spool actuation, etc. when driving on bumpy-ground, therefore an open loop joystick and open loop mini-steering wheel signal filter has been applied to the PVED-CLS’s steering wheel control algorithm.
OPEN LOOP MINI-WHEEL – VEHICLE SPEED DEPENDENT FAST-STEERING The PVED-CLS has five different open loop mini-steering wheel programs, where the desired number of turns lock-to- lock on the mini-steering wheel at a given vehicle speed (i.e. “Fast-steering”) can be setup.
11.4.1 Compensate steering sensitivity according to wheel angle range PVED-CLS offers a feature to keep the steering sensitivity fixed if the physical max wheel angle range is changed due to adding/changing tires. The native steering program sensitivities for the steering programs are defined for the native physical wheel angle range at programming time.
Page 102
The range is from 1° to 160° for P3706, in steps of 1°. For P3705 the range goes from 0% to 100% in steps of 1%. The values recommended by Danfoss are P3706 set to 20 and P3705 set to 15 i.e. anti-drift will be enabled all the time and 15% of the full flow will be added or deducted depending on direction, to the calculated ideal ccm per revolution- output, when the difference between the measured steering wheel position and the actual position of the wheels is 20°...
Jerk is a common unpleasant feeling/phenomenon, which can be experienced on large, articulated vehicles. To minimize these jerks, the PVED-CLS has a built-in anti-jerk algorithm, which can be enabled and parameterized. The anti-jerk function applies to all AUX Open Loop steering devices.
The range is from 0 to 1000 [IR] for P3710 and P3712 (i.e. relative wheel angle). The Danfoss recommended values are P3708 set to 200, and P3710 and P3712 set to 0. Soft stop functionality is disabled with default values.
11.8 OPEN LOOP JOYSTICK – TRANSFER FUNCTION While using open loop joystick with PVED-CLS it is possible to define a transfer function, which scales the open loop joystick position to a requested flow. The transfer function configuration can be done by configuring the below parameters •...
Page 109
1000 IR. • P3736 i.e. ‘AUX joystick - Dead-band region’ shall be less than or equal to P3738. PVED-CLS will enter safe state if these rules are not followed. Range Name Description of parameter...
OPEN LOOP JOYSTICK – VEHICLE SPEED DEPENDENT FLOW SCALING As a risk mitigation method, when using the open loop joystick functionality in AUX steering mode, the PVED-CLS’s AUX control algorithm can also limit and scale the maximum allowed output flow in proportion to the vehicle speed (i.e.
11.10 CLOSED LOOP JOYSTICK – VEHICLE SPEED DEPENDENT WHEEL ANGLE LIMITATION As a risk mitigation method, when using a Closed Loop Joystick function, the PVED-CLS’s Closed Loop Joystick control algorithm can limit the maximum allowed angle, that the wheels can be moved to, in proportion to the vehicle speed (i.e.
Page 112
Failure to comply with the above rules may render this function inoperable or lead to undesirable steering behavior! After a desired max wheel angle has been found by the PVED-CLS, in terms of the vehicle speed, the PVED-CLS will scale and interpolate to that max wheel angle, see example in Figure .
Page 113
In Figure , an example is shown, using the default parameters for parameters P3720 to P3724 (see Figure and Table 49). Figure is considering a vehicle speed of 15 km/h, where the corresponding max wheel angle is 10°. The PVED-CLS will scale, using interpolation, from AUX max wheel angle (left) to 0,0 and from 0,0 to AUX max wheel angle (right).
11.11 CLOSED LOOP JOYSTICK – VEHICLE SPEED DEPENDENT CLOSED LOOP CONTROL As each application is different, Danfoss has implemented a speed dependent closed loop control gain, configurable for Closed Loop Joystick. When using a Closed Loop Joystick function, the PVED-CLS’s Closed Loop Joystick-control algorithm can vary the closed loop gain, dependent on the vehicle speed.
All Remaining combinations Safe State Table 51 PVED-CLS also checks if the Joystick position status and X-axis position are consistent with each other, if not PVED- CLS triggers safe state. 11.12.2 Validation and Scaling of Elobau Joystick Position Error check on the received x-axis position signal is performed in both main and safety controller i.e. if received x-axis position is greater than 1000 then PVED-CLS will trigger safe state.
Table 52 Important The PVED-CLS will only handle byte 1 and 2 of BJM and EJM messages received from ELOBAU joystick, all other bytes are treated as “don’t cares” by the PVED-CLS and no checks will be performed on these.
When the PVED-CLS is in off-road steering mode (see Figure ) the Auto-guidance steering can be chosen. Furthermore, the PVED-CLS can be configured in such a way, that two auto-guidance controllers (GPS and GPS2) can be interfaced. Two safety functions for auto-guidance controllers (GPS and GPS2) can be configured, which can be enabled and run simultaneously.
P3583 and P3584. The PVED-CLS detects that the steering wheel is used when both the threshold P3583 and P3584 are being exceeded. In order to switch to auto-guidance program from STW or AUX program, following conditions shall be satisfied •...
VEHICLE SPEED DEPENDENT WHEEL ANGLE LIMITATION As a risk mitigation method, when using an auto-guidance function, the PVED-CLS’s auto-guidance control algorithm can limit the maximum allowed angle, that the wheels can be moved to, in proportion to the vehicle speed (i.e. the faster the vehicle goes, the narrower the maximum allowed angle, that the wheel can be moved to, will be).
Page 125
Point U “Closed loop gain” is valid for Point U “Vehicle speed” and vehicle speeds above Point U “Vehicle speed” Important Danfoss recommends using fixed gain. Use speed dependent gain only if necessary. GPS - Vehicle speed dependent closed loop control Point U...
GPS algorithm type = GPS v1 Using the auto-guidance function, the PVED-CLS’s auto-guidance control algorithm can also limit the maximum allowed output flow in proportion to the vehicle speed (i.e. the faster the vehicle goes the lower the maximum allowed flow will be).
GPS algorithm type = GPS v2 Using the auto-guidance function, the PVED-CLS’s auto-guidance control algorithm can also limit the maximum allowed wheel angle speed in proportion to the vehicle speed (i.e. the faster the vehicle goes the lower the maximum wheel angle speed will be).
If powering off the PVED-CLS is not feasible, Danfoss has implemented an option to use the PVED-CLS to broadcast wheel angle position on the CAN bus. This functionality will do a soft shut down of the PVED-CLS, to fulfill that the PVED-CLS is active for broadcasting signals on the CAN bus, when driving on road, but no controlling of the EH is available (hence SVB and Cut-off valve are off).
10ms). If the system is in a good condition, the confidence counter is decremented by 10ms*P3125. If the confidence counter is greater than equal to P3126, the fault condition flag is set and PVED-CLS enters safe state (unless disabled by parameter P3132). The fault condition flag is found in status message 5, byte 2, bits 2 – 1.
Parameter configuration is only possible in “bootloader-mode”! If the fault is related to the sensors or CAN bus cable tree, these faults should be resolved and the PVED-CLS should be powered up again. If the fault requires parameters to be changed, the PVED-CLS must brought into “bootloader- mode”...
Operational 1. Hoses between valve and steering actuator are swapped 2. Parameter; Invert Flow Direction; (P3080), is set to 255 and PVED-CLS is mounted on a OSPE/EHi or P3080 is set to 0 and PVED-CLS is mounted on a EHPS...
PLUS+1 Service tool • Other topics related to the steering system If further information to any errata is required, please contact your nearest Danfoss Product Application Engineer Attention • The system integrator and/or responsible for the target system is advised to periodically observe the errata information as new information will be added as needed.
DTC’s Diagnostic functions: This section lists all failures detected by diagnostic functions Internal Hardware: This section lists all failures found on the internal PCB in PVED-CLS Software: This section lists all failures detected inside the software Monitoring: This section lists all failures detected by crosscheck input signal and calculation results on SPI...
Page 143
- Most severe Severe Ambient Temperature is below -40 °C. level 0 - Data valid, but above normal Ambient Temperature + self-heating of PVED-CLS (~15 °C) is above 120 I/O Signals 520195 Temperature Sensor too high operational range - Most severe Severe °C.
Page 146
520583 LVDT calculation Severe Internal failure calculation out of range incorrect Software does not match peer PVED-CLS main controller contains a different software version than the PVED- Software 1563 Software Mismatch 31 - Condition exists Severe controller CLS safety controller...
17.3 FMI LIST In PVED-CLS the standard FMI from J1939-73 Appendix A page 130 are used as much as possible. However, in some cases some of the reserved area FMI’s are redefined to suit the need. The List of FMI’s used in PVED-CLS is found below:...
Resolution: 0.01 turns OSP displacement, number of cubic centimeters per revolution OSP displacement P3084 Note: When the PVED-CLS is mounted on an EHPS this parameter 1200 must be set equal to 0! Cylinder stroke volume. Acceptable values: 100-10000.
Resolution: 1 x10m/h = 10 meter pr. hour Safe state vehicle speed P3253 km/h The vehicle speed at which the PVED-CLS shall enter the safe state threshold EH-Steering disengage EH-Steering disengage method P3254 method Valid values: 0 (SASA); 1 (IMD: Internally Monitored Disengage)
Page 155
Valid Values: GMS message layout as 0 (Layout according to ISO11783-7:2009); P3326 per ISO11783 255 (Layout according to ISO11783-7:2015) See PVED-CLS communication protocol for clarification Transmission rate - P3327 x10mSec Default transmission rate of the Status Message 7 Status message 7...
ENGINEERING TOMORROW 17.4.15 OEM Data PVED-CLS reserves 100 bytes of EEPROM memory locations from address P4212 to P4311 for OEMs, system integrators can use these memory addresses to store their own data like serial ID or identification data. This EEPROM memory section is not CRC protected and no validation will be done by PVED-CLS.
Attention As a step in safe parameterization of the PVED-CLS software, to ensure the correctness of the data in one or more modified sectors it shall be signed. Signing off correctness is understood as it has been verified that all values in a sector are correct.
These counters will be updated automatically by the PLUS+1 Service Tool when using auto-calibration. If manual calibration is being used or a service tool is designed for themselves, Danfoss encourages to use these counter to keep track of the number of calibrations.
The following is a more detailed description of each main step: Read sensor values • Put PVED-CLS into “WAS calibration service mode” • Turn wheels into far left angle position Read primary wheel angle via CAN message and temporarily store the value Read secondary wheel angle via CAN message and temporarily store the value •...
Write parameters to PVED-CLS’ EEPROM Procedure: Read sensor values and sensor supply voltage • Put PVED-CLS into “Joystick Calibration service mode” • Start ADC readout on CAN bus For MAIN- and SAFETY-controller, start status message 1 @ 100ms For MAIN- and SAFETY-controller, start status message 3 @ 100ms •...
The PVED-CLS shall be put in “Service mode – direct output control”. Two initial test spool position set-points (test_db_R and test_db_L) shall be used. The calibration procedure will first initialize the steered wheels to the wheel angle given by Calib_WA_R.
Need help?
Do you have a question about the PVED-CLS and is the answer not in the manual?
Questions and answers