Installation guide
Electronic superheat controller
Type EKE 1D (PV02)
Introduction
Superheat controller EKE 1D is for use where superheat must be accurately controlled,
typically in commercial air conditioning, Commercial and industrial heat pumps, Commercial
refrigeration, food retailing and industrial applications.
Compatible valves: Danfoss ETS 6, ETS 8M (Bipolar) / ETS / ETS Colibri® / ETS L, KVS / KVS
Colibri® and CCM / CCMT / CCMT L / CTR valves.
Reference: For details please see EKE data sheet.
Applications
1. Superheat controller: standalone / network
ETS Colib ri®
2. Valve driver
ETS Colib ri®
Dimensions in mm
EKE 1D
Weight: 152 gram
© Danfoss | Climate Solutions | 2024.03
Communication
S2
Pe
Reference signal
Reference signal
S2
Pe
CAN RJ
70
60
ENGINEERING
T O M O R R O W
English
More info
Danfoss
Danfoss
R64-3033.10
R64-3033.10
Danfoss
80G8215.11
AN325741271542en-000406 | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PV02 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss PV02

  • Page 1 Commercial and industrial heat pumps, Commercial refrigeration, food retailing and industrial applications. Compatible valves: Danfoss ETS 6, ETS 8M (Bipolar) / ETS / ETS Colibri® / ETS L, KVS / KVS Colibri® and CCM / CCMT / CCMT L / CTR valves.
  • Page 2: Technical Specifications

    Stepper valves: A1, A2, A3, A4 Bipolar stepper motor output: - Danfoss ETS 8M (Bipolar) / ETS C / ETS L / KVS / KVS C / CCMT 2 – CCMT 42 / CCMT L / CTR Valves Other Valves:...
  • Page 3: Other Features

    (“damage”) resulting from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper use of the product.
  • Page 4 ANALOG / DIGITAL INPUT CAN - RJ CAN RJ CAN RJ Superheat controller Superheat controller EKE 1B - 080G5350 STEPPER VALVE DIGITAL OUTPUT PWR 24V Vbat STEPPER VALVE DIGITAL OUTPUT AN325741271542en-000406 | 4 © Danfoss | Climate Solutions | 2024.03...
  • Page 5 18 V Relay Power Normally open or 2.5 A Batt normally closed backup T fuse (optional) (optional) (optional) ETS6 valve Alarm ON/OFF solenoid ETS / KVS valve Colibri® CCMT/CTR valves AN325741271542en-000406 | 5 © Danfoss | Climate Solutions | 2024.03...
  • Page 6 CAN RJ CAN RJ Superheat controller Superheat controller Superheat controller Superheat controller Superheat controller Superheat controller EKE 1x - 080G5xxx EKE 1x - 080G5xxx EKE 1x - 080G5xxx Power supply AN325741271542en-000406 | 6 © Danfoss | Climate Solutions | 2024.03...
  • Page 7 • Terminal resistors 120 Ω for terminal devices are recommended at both ends of the bus, Terminal resistance between H and L terminals. • The default unit address is 1, which can be changed using parameter “G001 Controller adr". CANbus Not in use Danfoss 84N404.10 AN325741271542en-000406 | 7 © Danfoss | Climate Solutions | 2024.03...
  • Page 8 • The stepper motor is connected to the “Stepper Valve” terminals (see terminal assignment) with a standard M12 connection cable. • To configure stepper motor valves other than Danfoss stepper motor valves, the correct valve parameters must be set as described in the Valve configuration section (see manual for details).
  • Page 9: Led Indication

    • Place cable holder close to MMIMYK to keep USB connector firmly in place. • Keep USB cable length < 1 m. • Place MMIMYK and route USB cable far from noise sources (inverter, motors, contactors etc.) AN325741271542en-000406 | 9 © Danfoss | Climate Solutions | 2024.03...
  • Page 10 Note: Setup and service menu requires login with the default password 100 ( daily use), 200 (service use) or 300 (commissioning use). Long press Enter key to access login menu. AN325741271542en-000406 | 10 © Danfoss | Climate Solutions | 2024.03...
  • Page 11: Status Menu

    Setup wizard via MMIGRS2 display When all connections to the controller have been made, after the power is switched on, the Danfoss logo will appear for 5 seconds, then the Home screen will be displayed. To access the Wizard: press and hold enter to access the Login screen, the commissioning password is 300, scroll down the Setup and service menu and select “Setup wizard”.
  • Page 12 The setting will depend on the system requirement. Parameter: R012 Main Switch Select valve type Select predefined Danfoss valve type ETS, ETS C, KVS, KVS C, CCM, CCMT, CTR, or user defined. Parameter: I067 Valve configuration Application mode...
  • Page 13 5 = NSK | 6 = AKS 32 1-5V | 7 = OEM Voltage | 8 = Bus shared, 9 =DST P110 O020 Pe transmitter min. Define pressure range in bar gauge 550C (in bar g) O021 Pe transmitter max. Define pressure range in bar gauge 550C (in bar g) AN325741271542en-000406 | 13 © Danfoss | Climate Solutions | 2024.03...
  • Page 14 Range 2 – 9 K N116 SH ref. delta temp. 550B Range 20 – 100 factor ( %) For a detailed parameter list and explanation, please check the EKE data sheet. AN325741271542en-000406 | 14 © Danfoss | Climate Solutions | 2024.03...
  • Page 15: Related Products

    M12 cable ACCCBI cables for MMI display and gateway. EKE is compatible with Danfoss stepper M12 Angle cable to connect motor valves i.e Danfoss ETS 6, ETS, KVS, Danfoss stepper motor valve and ETS Colibri®, KVS colibri®, CTR, CCMT EKE controller AN325741271542en-000406 | 15 ©...

This manual is also suitable for: