WEST P8700 User Manual page 88

1/4, 1/8 and 1/16 din plus series controllers & indicators
Table of Contents

Advertisement

1
1
1
/
-DIN,
/
-DIN &
/
4
8
16
Parameter
Serial Number Low
Serial Number Mid
Serial Number High
Date of
manufacture
Product Revision
Level
Firmware Version
Input status
Option Slot 2
Re-transmit output
Maximum
Option Slot 2
Re-transmit output
Minimum
Option Slot 3
Re-transmit output
Maximum
Option Slot 3
Re-transmit output
Minimum
Note:
Some of the parameters that do not apply to a particular configuration will accept reads
and writes (e.g. attempting to scale a Linear output which has not been fitted). Read only
parameters will return an exception if an attempt is made to write values to them.
59305, Issue 5 – March 2005
- DIN Controllers & Indicators - Product Manual
Modbus
ASCII Ident &
Parameter No.
Message Types
123
RO
124
RO
125
RO
126
RO
RO
129
130
RO
133
RO
2224
R/W
2225
R/W
2234
R/W
2235
R/W
Notes
Digits aaaa
Digits bbbb
Digits cccc
Manufacturing date code as an
encoded binary number.
E.g. 0403 for April 2003 is returned as
193hex
Low Byte
High Byte
Bits
0 - 4
5 - 9
10 - 15
Input status. Read Only.
Bit 0: Sensor break flag
Bit 1: Under-range flag
Bit 2: Over-range flag
Maximum scale value for retransmit
output in slot 2, 1999 to 9999.
Minimum scale value for retransmit
output in slot 2, 1999 to 9999.
Maximum scale value for retransmit
output in slot 3, 1999 to 9999.
Minimum scale value for retransmit
output in slot 3, 1999 to 9999.
P6700, P8700 & P4700 Model Group
Unit serial number.
Format aaaa bbbb
cccc, (12 BCD digits).
Alpha part of PRL.
E.g. A = 01hex
Numeric part of PRL.
E.g. 13 = 0Dhex
Meaning
Revision number (1,2...)
Alpha version (A=0,
B=1...)
Numeric version
(starting from 121 = 0)
Page 69

Advertisement

Table of Contents
loading