Recalibration Procedure

Recalibration is carried out in five phases as shown in the table below, each phase
corresponds to an input range of the instrument.
CAUTION:
The 50mV phase MUST be calibrated before the thermocouple range.
<-B2'
<-B3
'
<-B4
<-BE'
<-BG'
To start calibration, apply the required calibration input from the source type list above, using
the correct connections,
1. Whilst the instrument is powering up, press
Note:
If a phase has not been previously calibrated the display will flash.
2. Press
to initiate calibration on PID Controllers, or
Press
to initiate calibration on Limit Controllers, or
Press
and
3. During calibration the display changes to 8888 for a few seconds.
4. If the input is misconnected or an incorrect signal is applied the calibration will be aborted
and the display will shown &5<+ . The previous calibration value will be retained.
5. If the calibration has succeeded, the pass display is shown <-B2 '(non-flashing).
6. Press
to step onto the next phase.
7. Repeat this process for each input type until all the phases are calibrated.
Note:
Switch off the instrument to exit the Calibration Mode.
Calibration Mode automatically exits if there is no button activity for five minutes.
59305, Issue 5 – March 2005
- DIN Controllers & Indicators - Product Manual

Table 36. Input Calibration phases

50 mV
10 V
20 mA
RTD input (200 ohm)
Thermocouple (K type source at 0ºC required)
together to initiate calibration on Indicators.
together until <-B2 is displayed.
and
Calibration
Page 105