P6010 & P8010 Indicators - Serial Communications Parameters; Bit Parameters; Table 24. P6010 & P8010 Communications - Bit Parameters - WEST P8700 User Manual

1/4, 1/8 and 1/16 din plus series controllers & indicators
Table of Contents

Advertisement

P6010 & P8010 Indicators – Serial Communications Parameters
The Modbus parameter addresses, and the possible ASCII message types and parameters
indents for the P6010 & P8010 are detailed below. RO indicates a parameter is read only,
WO indicates a parameter is write only and R/W indicates it can read from or written to.
Communications writes will not implemented if the Communications Write Parameter is
disabled. Refer to the Modbus and ASCII Communications sections of this manual for details
of the protocols used.

Bit Parameters

Bit parameters are not applicable to the ASCII protocol.
Table 24. P6010 & P8010 Communications - Bit Parameters
Parameter
Alarm 1 Status
Alarm 2 Status
Alarm 3 Status
Alarm 1 Latched
PV Under Range
PV Over Range
Sensor Break
Latched Alarm
Reset
Reset Maximum PV
Reset Minimum PV
Reset Elapsed
Time
Alarm 5 Status
Alarm 5 Status
Alarm 2 Latched
Alarm 3 Latched
Alarm 4 Latched
Alarm 5 Latched
To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section
*Note:
Alarm Latched status requests always returns 0 if that alarm is not configured to be
latching.
Page 86
1
1
/
-DIN,
/
-DIN &
4
8
Modbus
Notes
Parameter No.
RO
1 = Active, 0 = Inactive
1
2
RO
1 = Active, 0 = Inactive
3
RO
1 = Active, 0 = Inactive
4
RO
1 = Alarm 1 Latched, 0 = Not Latched*
5
RO
1 = PV Under-range, 0 = PV within range
6
RO
1 = PV Over-range, 0 = PV within range
7
RO
1 = Sensor Break Active, 0 = Sensor Break Inactive
8
WO
Writing any value resets all latched alarm relays.
Note: Outputs will only reset if their alarm condition
is no longer present.
9
WO
Writing any value resets the stored maximum displayed
PV value
10
WO
Writing any value resets the stored minimum displayed
PV value
11
WO
Writing any value resets the stored alarm 1 active time
value
12
RO
1 = Active, 0 = Inactive
13
RO
1 = Active, 0 = Inactive
14
RO
1 = Alarm 2 Latched, 0 = Not Latched*
RO
1 = Alarm 3 Latched, 0 = Not Latched*
15
16
RO
1 = Alarm 4 Latched, 0 = Not Latched*
17
RO
1 = Alarm 5 Latched, 0 = Not Latched*
P6010 & P8010 Model Group
1
/
- DIN Controllers & Indicators - Product Manual
16
59305, Issue 5 – March 2005