RTD Performance

Type:
Calibration:
Measurement
Accuracy:
Linearisation
Accuracy:
Temperature
Stability:
Supply Voltage
Influence:
Relative Humidity
Influence:
Sensor Resistance
Influence:
Lead Compensation:
RTD Sensor Current:
Sensor Break
Protection:

DC Linear

DC Linear Ranges Available

0 to 20mA
4 to 20mA (default)

DC Linear Performance

Scale Range Upper Limit:
Scale Range Lower Limit:
Minimum Span:
Measurement Accuracy:
Temperature stability:
Supply Voltage Influence:
Relative Humidity
Influence:
Input Protection:
Sensor Break Protection:
59305, Issue 5 – March 2005
- DIN Controllers & Indicators - Product Manual
Three-wire Pt100.
Complies with BS1904 and DIN43760 (0.00385Ω/Ω/°C).
±0.1% of span ±1LSD.
Better than ±0.2°C any point, any 0.1°C range (±0.05°C typical). Better
than ±0.5°C any point, any 1°C range.
0.01% of span/°C change in ambient temperature.
Negligible.
Negligible.
Pt100 50Ω/lead: <0.5% of span error.
Automatic scheme.
150µA (approximately).
Break detect approx two seconds. Control outputs turn OFF (0% power);
Limit outputs turn off (goes into Exceed condition); Alarms operate as if
the process variable has gone over-range.
0 to 50mV
10 to 50mV
–1999 to 9999. Decimal point as required.
–1999 to 9999. Decimal point as for Scale Range Upper Limit.
1 display LSD.
±0.1% of span ±1LSD.
0.01% of span/°C change in ambient temperature.
Negligible.
Negligible.
Up to 10 times maximum span of selected input connection.
Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Break detect approx two seconds. Control outputs turn OFF (0%
power); Limit outputs turn off (goes into Exceed condition); Alarms
operate as if process variable is under-range.
0 to 5V
1 to 5V
0 to 10V
2 to 10V