Power Connections - Mains Powered Instruments

Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply. Power
consumption is 7.5VA. Connect the line voltage (live and neutral) as illustrated via a two-pole
isolating switch (preferably located near the equipment) and a 1amp anti-surge fuse. If the
instrument has relay outputs with contacts carrying mains voltage, it is recommended that
the relay contacts supply should be switched and fused in a similar manner, but should be
separate from the instruments mains supply.
9
10
WARNING:
CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT
VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY.
CAUTION:
This equipment is designed for installation in an enclosure that provides adequate
protection against electric shock

Power Connections - 24/48V AC/DC Powered Instruments

24/48V AD/DC powered instruments will operate from a 20 to 48V AC or 22 to 55V DC
supply. AC power consumption is 7.5VA max, DC power consumption is 5 watts max.
Connection should be via a two-pole isolating switch (preferably located near the equipment)
and a 315mA slow-blow (anti-surge type T) fuse.
9
10
WARNING:
CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT
VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY.
59305, Issue 5 – March 2005
- DIN Controllers & Indicators - Product Manual
1
/
DIN
16
Figure 13.
Mains Power Connections
_
1
/
DIN
16
Figure 14.
24/48V AC/DC Power Connections
L
13
14
N
1
/
4
13
14
+
1
/
4
Connections
L
N
1
DIN &
/
DIN
8
+
1
DIN &
/
DIN
8
_
Page 17

Advertisement

Table of Contents
loading

Table of Contents