Option Slot 2 - Relay Module; Option Slot 2 - Ssr Driver Module; Option Slot 2 - Triac Module; Figure 22. Option Slot 2 - Relay Module - WEST P8700 User Manual

1/4, 1/8 and 1/16 din plus series controllers & indicators
Table of Contents

Advertisement

Option Slot 2 - Relay Module

If option slot 2 is fitted with a relay output module, make connections as illustrated.
The contacts are rated at 2 amp resistive 120/240 VAC.

Option Slot 2 - SSR Driver Module

If option slot 2 is fitted with an SSR driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load impedance must be no less than 500
ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs.

Option Slot 2 - Triac Module

If option slot 2 is fitted with a triac output module, make connections as illustrated.
The triac is rated at 0.01 to 1 amp @ 240V AC 50/60Hz