Option Slot 1 - Relay Module; Option Slot 1 - Ssr Driver Module; Option Slot 1 - Triac Module; Figure 18. Option Slot 1 - Relay Module - WEST P8700 User Manual

1/4, 1/8 and 1/16 din plus series controllers & indicators
Table of Contents

Advertisement

Option Slot 1 - Relay Module

If option slot 1 is fitted with a relay output module, make connections as illustrated. The relay
contacts are rated at 2 amps resistive, 120/240 VAC.

Option Slot 1 - SSR Driver Module

If option slot 1 is fitted with an SSR driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load impedance must be no less than 500
ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs.

Option Slot 1 - Triac Module

If option slot 1 is fitted with a Triac output module, make connections as illustrated. The triac
output is rated at 0.01 to 1 amp @ 240V AC 50/60Hz.
Page 20
1
1
/
-DIN,
/
-DIN &
4
8
1
N/O
2
COM
N/C
3
1
/
DIN
16
Figure 18.
Option Slot 1 – Relay Module
1
+
2
3
_
1
/
DIN
16
Figure 19.
Option Slot 1 - SSR Driver Module
1
2
1
/
DIN
16
Figure 20.
Option Slot 1 - Triac Module
Connections
1
/
- DIN Controllers & Indicators - Product Manual
16
19
20
21
1
/
DIN &
4
1
/
DIN &
4
20
21
1
/
DIN &
4
N/C
COM
N/O
1
/
DIN
8
19
_
20
21
+
1
/
DIN
8
1
/
DIN
8
59305, Issue 5 – March 2005