How to perform the limited start-up
Before you start, ensure that you have the motor nameplate data on hand.
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
procedure.
The drive will start up automatically at power up, if the external run command is on.
Check the installation. See the checklist in chapter Installation, page 31.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
• there is a risk of damage in case of incorrect direction of rotation, or
• an ID Run can be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
Apply input power.
Select MENU to enter the main menu.
Select the Parameters mode with keys
ENTER to select the Parameters mode.
Select the Start-Up Data group with keys
select SEL.
Select the application macro (parameter 9902) with keys
. Select EDIT to change the parameter value. The default
value 6 (
PID CONTROL
Press keys
Select SAVE to store the modified value or select CANCEL to
leave the set mode. Any modifications not saved are cancelled.
SAFETY
POWER-UP
) is suitable in most cases for pumping.
/
to change the parameter value.
Safety
must be followed during the start-up
/
and select
/
and
/
Start-up, control with I/O and ID Run
35
PID CONTROL
PID CONTROL