ABB ACQ550-x1-06A6-2 User Manual page 260

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

260
Alarm
code
2018
(Note 1)
2019
2020
2021
2022
2023
2024
2025
2026
2027
2028
Note 1. Even when the relay output is configured to indicate alarm conditions (e.g. parameter
Diagnostics
Display
This alarm warns that the PID sleep function is active, which means
PID SLEEP
that the motor could accelerate when the PID sleep function ends.
• To control PID sleep, use parameters 4022...4026 or 4122...4126.
Performing ID Run.
ID RUN
Not used.
RESERVED
1
This alarm warns that the Start Enable 1 signal is missing.
START ENABLE
MISSING
• To control Start Enable 1 function, use parameter 1608.
To correct, check:
• Digital input configuration.
• Communication settings.
2
This alarm warns that the Start Enable 2 signal is missing.
START ENABLE
MISSING
• To control Start Enable 2 function, use parameter 1609.
To correct, check:
• Digital input configuration.
• Communication settings.
Emergency stop activated.
EMERGENCY
STOP
OBSOLETE
Signals that a the drive is performing a First Start evaluation of motor
FIRST START
characteristics. This is normal the first time the motor is run after motor
parameters are entered or changed. See parameter 9910
description of motor models.
Not used.
RESERVED
This alarm warns that the condition defined by parameter 3701
USER LOAD
CURVE
LOAD C MODE
3703
Shown during the Start delay. See parameter 2113
START DELAY
1401
1 = 5 (
RELAY OUTPUT
output.
Description
has been valid longer than half of the time defined by
.
USER LOAD C TIME
) or 16 (
/
)), this alarm is not indicated by a relay
ALARM
FLT
ALARM
ACQ550-U1 User's Manual
for a
ID RUN
USER
.
START DELAY