ACQ550-U1 User's Manual
Code
5309
5310
5311
5314
5315
5316
Description
EFB STATUS
EFB PAR10
EFB PAR11
EFB PAR14
EFB PAR15
EFB PAR 16
EFB Protocol Reference
Modbus
This parameter indicates the internal status of the EFB
Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving
messages.
• TIMEOUT – Time between valid messages has
exceeded the interval set by parameter 3019.
• OFFLINE – EFB Protocol is receiving messages NOT
addressed to this drive.
• ONLINE – EFB Protocol is receiving messages
addressed to this drive.
• RESET – EFB Protocol is in reset.
• LISTEN ONLY – EFB Protocol is in listen-only mode.
Not used for Comm
Sets the response turnaround time
setup.
in milliseconds in addition to any
fixed delay imposed by the protocol.
When this protocol is selected, the
default value is: 5 ms
Not used for Comm
This parameter, together with
setup.
parameter 5317,
BACnet Device Object Instance
IDs:
• For the range 1 to 65,535: This
• For IDs > 65,335: The ID equals
Not used for Comm setup.
Not used for Comm setup.
Not used for Comm
This parameter indicates the count of
setup.
MS/TP tokens passed to this drive.
BACnet
17, sets
EFB PAR
parameter sets the ID directly
(5317 must be 0). For example,
the following values set the ID to
49134: 5311 = 49134 and 5317 =
0.
5311's value plus 10,000 times
5317's value. For example, the
following values set the ID to
71234: 5311 = 1234 and 5317 =
7.
Embedded fieldbus
183