ABB ACQ550-x1-06A6-2 User Manual page 149

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

ACQ550-U1 User's Manual
Code Description
Analog input reference correction
Parameter values 9, 10 and 14...17 use the formula in the following table.
Value setting
C + B
C value + (B value - 50% of reference value)
C * B
C value · (B value / 50% of reference value)
C - B
(C value + 50% of reference value) - B value
C / B
(C value · 50% of reference value) / B value
Where:
• C = Main reference value
( =
for values 9, 10 and
COMM
=
1 for values 14...17)
AI
• B = Correcting reference
( =
1 for values 9, 10 and
AI
=
2 for values 14...17).
AI
Example:
The figure shows the reference source curves for
value settings 9, 10 and 14...17, where:
• C = 25%.
• P 4012
SETPOINT MIN
• P 4013
SETPOINT MAX
• B varies along the horizontal axis.
4011 INTERNAL SETPNT
Sets a constant value used for the process reference.
• Units and scale are defined by parameters 4006 and 4007.
4012 SETPOINT MIN
Sets the minimum value for the reference signal source.
• See parameter 4010.
4013 SETPOINT MAX
Sets the maximum value for the reference signal source.
• See parameter 4010.
4014 FBK SEL
Defines the PID controller feedback (actual signal).
• You can define a combination of two actual values (
• Use parameter 4016 to define the source for actual value 1 (
• Use parameter 4017 to define the source for actual value 2 (
1 =
1 – Actual value 1 (
ACT
2 =
1-
2 –
ACT
ACT
ACT
3 =
1+
2 –
ACT
ACT
ACT
4 =
1 *
2 –
ACT
ACT
ACT
5 =
1/
2 –
ACT
ACT
ACT
6 =
(
1,2) – The smaller of
MIN
ACT
7 =
(
1,2) – The greater of
MAX
ACT
8 = sqrt(
1-2) – Square root of the value for
ACT
9 = sq
1+sq
2 – Square root of
A
A
10 = sqrt(
1) – Square root of
ACT
11 =
1 – Signal 0158
COMM FBK
12 =
2 – Signal 0159
COMM FBK
13 =
(
1,2) – The average of
AVE
ACT
4015 FBK MULTIPLIER
Defines an extra multiplier for the PID feedback value FBK defined by parameter 4014.
• Used mainly in applications where the flow is calculated from the pressure difference.
0.000 =
– The parameter has no effect (1.000 used as the multiplier).
NOT SEL
-32.768...32.767 – Multiplier applied to the signal defined by parameter 4014
Example:
FBK
Multiplier
=
Calculation of the AI reference
= 0.
= 0.
1) provides the feedback signal.
ACT
1 minus
2 provides the feedback signal.
ACT
1 plus
2 provides the feedback signal.
ACT
1 times
2 provides the feedback signal.
ACT
1 divided by
2 provides the feedback signal.
ACT
1 or
2 provides the feedback signal.
ACT
ACT
1 or
2 provides the feedback signal.
ACT
ACT
ACT
1 plus the square root of
ACT
1 provides the feedback signal.
ACT
PID COMM VALUE
PID COMM VALUE
1 and
ACT
ACT
A1 A2
120
17 (/)
100
80
60
40
20
0
0
1 and
2) as the feedback signal.
ACT
ACT
1).
ACT
2).
ACT
1 minus
2 provides the feedback signal.
ACT
2 provides the feedback signal.
ACT
1 provides the feedback signal.
2 provides the feedback signal.
2 provides the feedback signal.
100%
.
FBK SEL
Parameters
149
9, 14 (+)
10, 15 ( * )
16 (-)
B