ABB ACQ550-x1-06A6-2 User Manual page 254

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

254
Fault
code
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Diagnostics
Fault name in
panel
Motor or process stall. Motor is operating in the stall region. Check for and
MOTOR STALL
correct:
• Excessive load.
• Insufficient motor power.
• Parameters 3010...3012.
Not used.
RESERVED
1
Digital input defined to report first external fault is active. See parameter
EXT FAULT
3003
EXTERNAL FAULT
2
Digital input defined to report second external fault is active. See parameter
EXT FAULT
3004
EXTERNAL FAULT
Possible ground fault detected in the motor or motor cables. The drive
EARTH FAULT
monitors for ground faults while the drive is running and while the drive is
not running. Detection is more sensitive when the drive is not running and
can produce false positives.
Possible corrections:
• Check for/correct faults in the input wiring.
• Verify that motor cable does not exceed maximum specified length.
• A delta grounded input power supply and motor cables with high
capacitance may result in erroneous error reports during non-running
tests. To disable response to fault monitoring when the drive is not
running, use parameter 3023
ground fault monitoring, use parameter 3017
Note: Disabling earth fault (ground fault) may void the warranty.
Not used.
OBSOLETE
Internal fault. The thermistor measuring the internal temperature of the
THERM FAIL
drive is open or shorted. Contact your local ABB representative.
Internal fault. A communication-related problem has been detected on the
OPEX LINK
fiber optic link between the control and OINT boards. Contact your local
ABB representative.
Internal fault. Exceptionally low voltage detected on the OINT power supply.
OPEX PWR
Contact your local ABB representative.
Internal fault. Current measurement is out of range. Contact your local ABB
CURR MEAS
representative.
Ripple voltage in the DC link is too high. Check for and correct:
SUPPLY PHASE
• Missing mains phase.
• Blown fuse.
OBSOLETE
Motor speed is greater than 120% of the larger (in magnitude) of 2001
OVERSPEED
MINIMUM SPEED
• Parameter settings for 2001 and 2002.
• Adequacy of motor braking torque.
• Applicability of torque control.
• Brake chopper and resistor.
Not used.
RESERVED
Internal fault. Configuration Block Drive ID is not valid. Contact your local
DRIVE ID
ABB representative.
Internal configuration file has an error. Contact your local ABB
CONFIG FILE
representative.
Description and recommended corrective action
1.
2.
WIRING FAULT
or 2002
MAXIMUM SPEED
ACQ550-U1 User's Manual