ABB ACQ550-x1-06A6-2 User Manual page 107

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

ACQ550-U1 User's Manual
Code Description
1605 USER PAR SET CHG
Defines control for changing the user parameter set.
• See parameter 9902
• The drive must be stopped to change User Parameter Sets.
• During a change, the drive will not start.
Note: Always save the User Parameter Set after changing any parameter settings, or performing a motor
identification.
• Whenever the power is cycled, or parameter 9902
saved. Any unsaved changes to a user parameter set are lost.
Note: The value of this parameter (1605) is not included in the User Parameter Sets, and it does not change if User
Parameter Sets change.
Note: You can use a relay output to supervise the selection of User Parameter Set 2.
• See parameter 1401.
0 =
– Defines the control panel (using parameter 9902) as the only control for changing User Parameter
NOT SEL
Sets.
1 =
1 – Defines digital input
DI
• The drive loads User Parameter Set 1 on the falling edge of the digital input.
• The drive loads User Parameter Set 2 on the rising edge of the digital input.
• The User Parameter Set changes only when the drive is stopped.
2...6 =
2...
6 – Defines digital input
DI
DI
• See
1 above.
DI
-1 =
1(
) – Defines an inverted digital input
DI
INV
• The drive loads User Parameter Set 1 on the rising edge of the digital input.
• The drive loads User Parameter Set 2 on the falling edge of the digital input.
• The User Parameter Set changes only when the drive is stopped.
-2...-6 =
2(
)...
DI
INV
DI
• See
1(
) above.
DI
INV
1607 PARAM SAVE
Saves all altered parameters to permanent memory.
• Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use
this parameter.
• If 1602
PARAMETER LOCK
must use this parameter.
• If 1602
PARAMETER LOCK
permanent memory.
0 =
– Value changes automatically when all parameters are saved.
DONE
1 =
... – Saves altered parameters to permanent memory.
SAVE
.
APPLIC MACRO
1 as a control for changing User Parameter Sets.
DI
2...
6 as a control for changing User Parameter Sets.
DI
DI
6(
) – Defines an inverted digital input
INV
= 2 (
), parameters altered from the control panel are not saved. To save, you
NOT SAVED
= 1 (
), parameters altered from the control panel are stored immediately to
OPEN
is changed, the drive loads the last settings
APPLIC MACRO
1 as a control for changing User Parameter Sets.
DI
2...
6 as a control for changing User Parameter Sets.
DI
DI
107
Parameters