ABB ACQ550-x1-06A6-2 User Manual page 274

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

274
Input power cables/wiring
Input wiring can be any of:
• a four conductor cable (three phases and ground/protective earth). Shielding is
not required.
• four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive's load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see section
276).
The table below lists copper and aluminium cable types for different load currents.
These recommendations apply only for the conditions listed at the top of the table.
Based on:
• EN 60204-1 and IEC 60364-5-2/2001
• PVC insulation
• 30 °C (86 °F) ambient temperature
• 70 °C (158 °F) surface temperature
• cables with concentric copper shield
• not more than nine cables laid on cable ladder
side by side.
Max. load
current
A
14
20
27
34
47
62
79
98
119
153
186
215
249
284
330
Technical data
IEC
Cu cable
Max. load
current
2
mm
A
3×1.5
Aluminium cable
cannot be used with
3×2.5
frame sizes R1...R5
because of its lower
3×4
capacity.
3×6
3×10
3×16
3×25
3×35
91
3×50
117
3×70
143
3×95
165
3×120
191
3×150
218
3×185
257
3×240
274
285
Drive's power connection terminals
Based on:
• NEC Table 310-16 for copper wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient temperature
• not more than three current-carrying
conductors in raceway or cable, or earth
(directly buried)
• copper cables with concentric copper shield.
Al cable
Max. load
current
2
mm
A
22.8
27.3
36.4
50.1
68.3
86.5
100
3×50
118
3×70
137
3×95
155
3×120
178
3×150
205
3×185
237
3×240
264
3× (3×50)
291
2× (3×95)
319
ACQ550-U1 User's Manual
on page
NEC
Cu wire size
AWG/kcmil
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM or 2 × 1
300 MCM or 2 × 1/0
350 MCM or 2 × 2/0