ABB ACQ550-x1-06A6-2 User Manual page 272

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

272
Check that the operating time of the fuse is below 0.5 seconds. The operating
time depends on the fuse type, the supply network impedance as well as the cross-
sectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with the gG or T fuses, ultra rapid (aR) fuses will in most
cases reduce the operating time to an acceptable level.
Fuses, 208...240 V drives
ACQ550-x1-
see below
-04A6-2
-06A6-2
-07A5-2
-012A-2
-017A-2
-024A-2
-031A-2
-046A-2
-059A-2
-075A-2
-088A-2
-114A-2
-143A-2
-178A-2
-221A-2
-248A-2
Fuses, 380...480 V drives
ACQ550-x1-
see below
-03A3-4
-04A1-4
-06A9-4
-08A8-4
-012A-4
-015A-4
-023A-4
-031A-4
-038A-4
-045A-4
-059A-4
-072A-4
-078A-4
-097A-4
Technical data
Input current
A
IEC 60269 gG (A)
4.6
10
6.6
7.5
11.8
16
16.7
25
24.2
30.8
40
46.2
63
59.4
74.8
80
88.0
100
114
125
143
200
178
250
221
315
248
Input current
A
IEC 60269 gG (A)
3.3
10
4.1
6.9
8.8
10
11.9
16
15.4
16
23
25
31
35
38
50
45
59
63
72
80
77
97
125
ACQ550-U1 User's Manual
Input power (mains) fuses
UL Class T (A)
10
JJS-10
15
JJS-15
25
JJS-25
25
JJS-25
40
JJS-40
60
JJS-60
80
JJS-80
100
JJS-100
110
JJS-110
150
JJS-150
200
JJS-200
250
JJS-250
300
JJS-300
350
JJS-350
Input power (mains) fuses
UL Class T (A)
10
JJS-10
10
JJS-15
16
JJS-15
16
JJS-20
30
JJS-30
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
90
JJS-90
100
JJS-100
80
JJS-110
Bussmann type
00467918.xls C
Bussmann type

Hide quick links:

Advertisement

Table of Contents
loading