ABB ACQ550-x1-06A6-2 User Manual page 182

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

182
Code
5303
5304
5305
5306
5307
5308
Embedded fieldbus
Description
EFB BAUD RATE
Defines the communication
speed of the RS485 link in
kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
76.8 kbits/s
EFB PARITY
Defines the data length, parity
and stop bits to be used with
the RS485 link communication.
• The same settings must be
used in all on-line stations.
0 = 8
1 – 8 data bits, No parity,
N
one stop bit.
1 = 8
2 – 8 data bits, No parity,
N
two stop bits.
2 = 8
1 – 8 data bits, Even
E
parity, one stop bit.
3 = 8
1 – 8 data bits, Odd
O
parity, one stop bit.
EFB CTRL PROFILE
Selects the communication
profile used by the EFB
protocol.
0 =
– Operation of
ABB DRV LIM
Control/Status Words
conform to ABB Drives
Profile (limited), as used in
ACQ550.
1 =
– Operation of
DCU PROFILE
Control/Status Words
conform to 32-bit DCU
Profile.
2 =
– Operation
ABB DRV FULL
of Control/Status Words
conform to ABB Drives
Profile (full).
EFB OK MESSAGES
EFB CRC ERRORS
EFB UART ERRORS
EFB Protocol Reference
Modbus
When this protocol is
When this protocol is selected, the
selected, the default
default value for this parameter is:
value for this
38400
parameter is: 9.6
When this protocol is
When this protocol is selected, the
selected, the default
default value for this parameter is: 0
value for this
Do not edit.
parameter is: 1
When this protocol is
N/A. When this protocol is selected,
selected, the default
the default value for this parameter
value for this
is: 0
parameter is: 0
Changing the value for this
parameter has no affect on this
protocol's behavior.
This parameter indicates the number of valid application
messages received at this drive. This count does not
include MS/TP token passing and polling messages. (For
such messages, see 5316).
This parameter indicates the number of CRC errors
detected, in either the header or data CRCs.
This parameter indicates the number of UART-related errors
(framing, parity) detected.
ACQ550-U1 User's Manual
BACnet

Hide quick links:

Advertisement

Table of Contents
loading