Actual values
The contents of the register addresses 40005...40012 are
• specified using parameters 5310...5317
• Read-only values containing information on the operation of the drive
• 16-bit words containing a sign bit and a 15-bit integer
• when negative values, written as the two's complement of the corresponding
positive value
• scaled as described earlier in section
Exception codes
Exception codes are serial communication responses from the drive. The ACQ550
supports the standard Modbus exception codes defined below.
Exception
code
01
02
03
Embedded fieldbus
Name
Unsupported Command
ILLEGAL FUNCTION
The data address received in the query is not allowable. It is not
ILLEGAL DATA ADDRESS
a defined parameter/group.
A value contained in the query data field is not an allowable
ILLEGAL DATA VALUE
value for the ACQ550, because it is one of the following:
• Outside min. or max. limits.
• Parameter is read-only.
• Message is too long.
• Parameter write not allowed when start is active.
• Parameter write not allowed when factory macro is selected.
ACQ550-U1 User's Manual
ACTUAL VALUES
Actual value scaling
on page 191.
Meaning