ABB ACQ550-x1-06A6-2 User Manual page 292

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

292
ACQ550-x1-
-038A-4
-045A-4
-059A-4
-072A-4
-078A-4
-097A-4
-125A-4
-157A-4
-180A-4
-246A-4
Air flow, 500...600 V drives
The following table lists heat loss and air flow data for 500...600 V drives.
ACQ550-U1-
-02A7-6
-03A9-6
-06A1-6
-09A0-6
-011A-6
-017A-6
-022A-6
-027A-6
-032A-6
-041A-6
-052A-6
-062A-6
-077A-6
-099A-6
-125A-6
-144A-6
Technical data
Drive
Frame size
R3
562
R3
667
R4
907
R4
1120
R4
1295
R4
1440
R5
1940
R6
2310
R6
2810
R6
3260
Drive
Frame size
R2
46
R2
68
R2
124
R2
170
R2
232
R2
337
R3
457
R3
562
R4
667
R4
907
R4
1120
R4
1295
R6
1504
R6
1821
R6
2442
R6
2813
Heat loss
W
BTU/hr
1919
2278
3098
3825
4423
4918
6625
7889
9597
11134
Heat loss
W
BTU/hr
157
232
423
581
792
1150
1560
1918
2276
3096
6820
4420
5136
6219
8339
9607
ACQ550-U1 User's Manual
Air flow
3
3
m
/h
ft
/min
134
79
280
165
280
165
280
165
280
165
250
147
404
238
404
238
404
238
540
318
00467918.xls C
Air flow
3
3
m
/h
ft
/min
88
52
88
52
88
52
88
52
88
52
88
52
134
79
134
79
280
165
280
165
280
165
280
165
404
238
404
238
404
238
404
238
00467918.xls C

Hide quick links:

Advertisement

Table of Contents
loading