ABB ACQ550-x1-06A6-2 User Manual page 222

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

222
Instance
ID
AV11
AV12
AV13
AV14
AV15
AV16
AV17
AV18
AV19
AV20
AV21
AV22
AV23
AV24
AV25
Embedded fieldbus
Object Name
PRC PID DEV
This object is the Process PID output
signal's deviation from its setpoint. The
corresponding drive parameter is 0132.
EXT PID FBCK
This object is the External PID feedback
signal. The corresponding drive
parameter is 0131.
EXT PID DEV
This object is the External PID output
signal's deviation from its setpoint. The
corresponding drive parameter is 0133.
RUN TIME (R)
This object indicates, in hours, the drive's
accumulated run time since the last reset.
The value can be reset to zero. The
corresponding drive parameter is 0114.
MOTOR TEMP
This object indicates the drive's motor
temperature, as set up in parameter
Group 35. The corresponding drive
parameter is 0145.
INPUT REF 1
This object sets Input Reference 1.
Control requires parameter 1103 value =
.
COMM
INPUT REF 2
This object sets either:
• Input Reference 2. Control requires
parameter 1106 value =
• Process PID setpoint. Control requires
parameter 1106 value =
parameter 4010 value =
LAST FLT
This object indicates the most recent fault
entered in the drive's fault log. The
corresponding drive parameter is 0401.
PREV FLT 1
This object indicates the second most
recent fault entered in the drive's fault
log. The corresponding drive parameter
is 0412.
PREV FLT 2
This object indicates the third most recent
fault entered in the drive's fault log. The
corresponding drive parameter is 0413.
AO 1 ACT
This object indicates Analog Output 1's
level. The corresponding drive parameter
is 0124.
AO 2 ACT
This object indicates Analog Output 2's
level. The corresponding drive parameter
is 0125.
ACCEL1 TIME
This object sets the Ramp1 acceleration
time. The corresponding drive parameter
is 2202.
DECEL1 TIME
This object sets the Ramp1 deceleration
time. The corresponding drive parameter
is 2203.
MBOX PARAM
This object defines the parameter to be
read or written to by the mailbox function.
See BV15 and BV16.
Description
.
COMM
1
and
PID
OUT
.
COMM
ACQ550-U1 User's Manual
Present Value
Units
Access Type
Percent
R
Percent
R
Percent
R
Hours
W
°C
R
Percent
C
Percent
C
None
R
None
R
None
R
Milliamps R
Milliamps R
Seconds
W
Seconds
W
None
W