Fault
Fault name in
code
28
SERIAL
29
EFB CON FILE
30
FORCE TRIP
31
EFB
32
EFB
33
EFB
34
MOTOR PHASE
35
OUTP WIRING
36
INCOMPATIBLE
SW
37
CB OVERTEMP
38
USER LOAD
CURVE
101...
SYSTEM ERROR
199
201...
SYSTEM ERROR
299
-
UNKNOWN
DRIVE TYPE
ACQ550
SUPPORTED
DRIVES
Description and recommended corrective action
panel
1
Fieldbus communication has timed out. Check for and correct:
ERR
• Fault setup (3018
• Communication settings
EFB PROTOCOL
• Poor connections and/or noise on line.
Error in reading the configuration file for the embedded fieldbus.
Fault trip forced by the fieldbus. See the fieldbus User's Manual.
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
The meaning is protocol dependent.
2
3
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
The drive cannot use the software.
• Internal fault.
• The loaded software is not compatible with the drive.
• Call support representative.
Drive control board is overheated. The fault trip limit is 88 °C. Check for and
correct:
• Excessive ambient temperature.
• Fan failure.
• Obstructions in the air flow.
Condition defined by parameter 3701
longer than the time defined by 3703
Error internal to the drive. Contact your local ABB representative and report
the error number.
Error in the system. Contact your local ABB representative and report the
error number.
Wrong type of panel, i.e. panel that supports drive X but not the ACQ550,
:
has been connected to the ACQ550.
:
X
and 3019
COMM FAULT FUNC
(Group 51: EXT COMM MODULE
as appropriate).
WIRING FAULT
USER LOAD C MODE
USER LOAD C TIME
).
COMM FAULT TIME
or
Group 53:
.
has been valid
.
Diagnostics