ABB ACQ550-x1-06A6-2 User Manual page 219

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

ACQ550-U1 User's Manual
Instance
ID
BV8
BV9
BV10
BV11
BV12
BV13
BV14
BV15
BV16
BV17
Object Name
AT SETPOINT
This object indicates whether
the drive is at the
commanded setpoint.
ENABLE ACT
This object indicates the
System Enable command
status (the combination of all
Run and Start Enables),
regardless of the control
source.
RUN/STOP CMD
This object commands a drive
start. Control requires either:
• Parameter 1001 value =
COMM
or
• Parameter 1002 value =
COMM
FWD/REV CMD
This object commands a
motor rotation direction
change. Control requires
1003 =
• Parameter 1001 value =
COMM
or
• Parameter 1002 value =
COMM
RUN ENA CMD
This object commands Run
Enable. Control requires
parameter 1601 value =
COMM
EXT 1/2 CMD
This object selects ext1 or
ext2 as the active control
source. Control requires
parameter 1102 value =
COMM
FAULT RESET
This object resets a faulted
drive. The command is rising-
edge triggered. Control
requires parameter 1604
value =
MBOX READ
This object reads a parameter
(defined by AV25
PARAM
MBOX DATA
MBOX WRITE
This object writes the data
value specified by AV26,
MBOX DATA
(defined by AV25,
PARAM
LOCK PANEL
This object locks the panel
and prevents parameter
changes. The corresponding
drive parameter is 1602.
Description
YES/NO
ENABLE/
DISABLE
RUN/STOP
for control by
1
EXT
for control by
2.
EXT
REV/FWD
and either:
REQUEST
for control by
1
EXT
for control by
2.
EXT
ENABLE/
DISABLE
.
EXT2/EXT1
.
RESET/NO
.
COMM
READ/RESET
MBOX
) and returns it in AV26
.
WRITE/RESET
, to a parameter
MBOX
).
LOCK/UNLOCK
Active/Inactive
Present Value
Text
Access Type
R
R
C
C
C
C
C
W
W
W
Embedded fieldbus
219

Hide quick links:

Advertisement

Table of Contents
loading