380...480 V drives
Type
ACQ550-
01/U1-
see below
Three-phase supply voltage, 380...480 V
-03A3-4
-04A1-4
-05A4-4
-06A9-4
-08A8-4
-012A-4
-015A-4
-023A-4
1
Resistor time constant specification must be > 85 seconds.
500...600 V drives
Type
ACQ550-
U1-
see below
Three-phase supply voltage, 500...600 V
-02A7-6
-03A9-6
-06A1-6
-09A0-6
-011A-6
-017A-6
1
Resistor time constant specification must be > 85 seconds.
WARNING! Never use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are not able to
handle the overcurrent caused by the low resistance.
Symbols
R
MIN
R
MAX
Resistance
< 3 s ON
R
R
MAX
MIN
> 27 s OFF
< 10% Duty
ohm
ohm
641
120
65
470
120
90
320
120
125
235
80
170
192
80
210
128
80
315
94
63
425
64
63
625
Resistance
< 3 s ON
R
R
MAX
MIN
> 27 s OFF
< 10% Duty
ohm
ohm
548
80
93
373
80
137
224
80
228
149
80
342
110
60
467
75
60
685
– Minimum allowed resistance of the braking resistor.
– Maximum resistance allowed if maximum braking torque is necessary.
1
Resistor
minimum continuous power rating
Deceleration-to-zero rating
P
P
r3
r10
< 10 s ON
< 30 s ON
> 50 s OFF
> 180 s OFF
< 17% Duty
< 14% Duty
W
W
120
175
160
235
235
345
320
470
400
575
590
860
800
1175
1175
1725
1
Resistor
minimum continuous power rating
Deceleration-to-zero rating
P
P
r3
r10
< 10 s ON
< 30 s ON
> 50 s OFF
> 180 s OFF
< 17% Duty
< 14% Duty
W
W
175
257
257
377
429
629
643
943
877
1286
1286
1886
P
P
Continuous ON
r30
r60
> 60 s ON
< 60 s ON
> 180 s OFF
> 25% Duty
< 25% Duty
W
W
285
1100
390
1500
570
2200
775
3000
950
4000
1425
5500
1950
7500
2850
11000
P
P
Continuous ON
r30
r60
> 60 s ON
< 60 s ON
> 180 s OFF
> 25% Duty
< 25% Duty
W
W
425
1462
624
2144
1040
3573
1560
5359
2127
7308
3119
10718
Technical data
287
P
rcont
W
P
rcont
W