D9412G/D7412G | Program Entry Guide | 1.0 Introduction
1.7
Programming the Control Panel
with the D5200 Programmer
Latch the jumper in the upper right hand corner of
the control panel labeled as RESET on the PCB and
Reset Pin on the faceplate.
Connect the molex end of the cord to the connector
labeled PROG on the PCB and PROG CONN on
the faceplate.
Always initiate a control panel copy at the
NEWRECORD or FILENAME display when pressing
the [RECV] (copy) key of the D5200.
Always initiate a control panel load at the
FILENAME
prompt or set as factory default at the
NEWRECORD
prompt when pressing the [SEND]
(load) key.
Disconnect the D5200 before releasing the reset pin.
Do not leave the D5200 connected to the
PROG connector without latching the
RESET pin. Doing so causes SDI ##
TROUBLE and CALL FOR SERVICE to
display on the command centers. Door
controllers also activate depending upon
the SDI failure DIP switch setting.

Table 5: Programming Error Displays

Display
INCOMPATIBLE PANEL
CHECK CORD/RESET
PIN
0101
There is a 5 second to 25 second pause
0101
after the reset pin is unlatched during
0101
which the control panel scans all the
points and properly displays, logs, and
reports them.
Bosch Security Systems | 10/03 | 47775E
Description
You are connected to the
wrong control panel or
using the wrong handler.
Check the faceplate for the
model number and the
handler title.
Check the cord and reset
pin