Chapter 6: Operating Dial Thermostats; Thermostat Components; Adjusting The Temperature; Replacing Batteries - Uponor Climate Control Zoning System II Installation And Operation Manual

Table of Contents

Advertisement

Chapter 6
Operating dial thermostats

Thermostat components

During normal operation, if there is a demand for heating, a
descreet LED on the dial thermostat is lit for about 60 seconds.
A
C
B
Figure 6-1: Dial thermostat components
Item
Description
A
Room temperature setpoint dial control
B
Heating demand LED
C
Backlight
D
Registration button
E
Disable timer switch (not used)
F
Batteries
F D E
F
Climate Control Zoning System II installation and operation manual | Chapter 6 – Operating dial thermostats l 23

Adjusting the temperature

The temperature is changed by adjusting the setpoint on
the thermostat to a value between 41°F to 95°F (5°C to 35°C).
Use the dial on the thermostat to adjust the temperature.
A backlight will light up when twisting the dial. It shuts off
after about 10 seconds of inactivity.
The illustration below shows how to adjust the thermostat
temperature setpoint.
Figure 6-2: Adjusting the thermostat setpoint
To adjust the thermostat temperature setpoint:
• Twist the dial clockwise for a higher temperature.
• Twist the dial counter-clockwise for a lower temperature.

Replacing batteries

Replace the batteries of the thermostat when the
LED flashes twice during a heating or cooling demand.
The thermostat will perform a self test, for about
10 seconds, when the batteries have been inserted.
The system will be blocked for input and the thermostat
LED flashes during this period.
The illustration below shows how to change batteries.
2
1
Figure 6-3: Replacing batteries
1. Angle the thermostat from the bracket.
2. Remove it from the wall.
3. Replace the batteries.
3

Advertisement

Table of Contents
loading

Table of Contents