Model 6820 / 6820-EVS Installation Manual
9.5.4
Point Programming For 5880, 5865, EVS-50W, EVS-INT50W,
EVS-100W, EVS-125W and EVS-CE4 Modules
To program 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W, or EVS-CE4 module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Then
press ENTER.
Select an output
group for this
Zone/Group
Select a name
for the Point
Figure 9-5 Programming Points as Outputs for the 5880 Module
Select Switch or Unused
Figure 9-6 Programming Points as Inputs for the 5880 Module
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrows to select the type (notification or unused). Press ENTER.
7.
Press the up or down arrows to select the desired group.
8.
Press ENTER.
9.
Edit point name. See Section 9.6. Or, press the right arrow to skip module name edit.
10. Repeat Steps 1 through 9 for all points.
9.5.5

Point Programming For EVS-VCM and EVS-RVM Modules

To program EVS-VCM and EVS-RVM module points:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press
ENTER.
5.
Enter the point number. Press ENTER.
6.
Press the up or down arrows to select the type (Switch or unused). Press ENTER.
7.
Press the up or down arrows to select the function. Press ENTER.
Select NOTIF or UNSED
Select Function
9-17
LS10144-001SK-E