View Group Points - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
single button press. See 11.2.3.2.
Key and LED Numbers
Figure 9-4 Corresponding Key and LED for Mapping Output Groups
Silencing Options
The following silencing options are available for each output group.
Optional
Timers
Silence Inhibit
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Auto Silence
Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
Auto Unsilence
If this option is selected, the output group can be silenced for a programmed time-frame. If the condition
that caused the output to activate has not cleared during the time-frame, the output reactivates. If you
select this option, select the time-frame in the delay field. Range is 0-60 minutes.
Startup Delay
When a alarm is generated, the Output group will not activate until the timer expires assuming the event
is still active. Range is 0-120 Seconds
9.4.2

View Group Points

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 2 to view group points.
5.
Enter the group number, then press ENTER.
Corresponding
EVS User Interface
Table 9-2: Silencing Options
Corresponding
Key and LED Numbers
EVS-SW24
Description
9-8
Programming